Research and Improvement of Fourier Algorithm in the Microcomputer Relay Protection

2013 ◽  
Vol 347-350 ◽  
pp. 1945-1948
Author(s):  
Jian Xu ◽  
Xin Yao

Fourier algorithm can be effective utilized in the Microcomputer relay protection to filter out Harmonic component in the AC signal .but the drawback is that not filter attenuation DC component. it may be affect the computation accuracy of the entire system .and it is also reduce the efficiency of the system. In this paper ,we combined with the actual project ,on the basis of analysis of the full-wave Fourier algorithm ,for the problem of it can not filter decaying a periodic component ,we proposed an improved algorithm, and combined with MATLAB simulation ,the results show that the improved algorithm has the advantages of high accuracy and the algorithm is simple. In the microcomputer relay protection of the power system need to handle all kinds of signals, provide the necessary information for the implementation of protection. however, With the rapid development of computer technology and the continuous research of computer algorithms, a lot of actual power system protection device has been widely used in our life, on the one hand, these devices reduce the complexity of building hardware circuit, on the other hand ,it can make full use of the filter function about some algorithms have itself. The most important is that it can avoid the problem of instability and low efficiency with some filter circuit. But, this characteristic need the algorithms has a high precision [2,3]. The algorithm is set up in the microcomputer protection is a mathematical model for achieve some specific function. and write the corresponding computer applications according to this model. Then do some specific mathematical operations with these digital signals will achieve the purpose of protection. At present, the widely used full wave Fourier algorithm has a function of filtering DC component and harmonic component[4],but it can not filtering the decaying DC component in the system. It will be cause a certain interference and influence to the whole system in the practical application, the result is that led to the precision of the operation drop and lose the meaning of the protecting. In this paper, combined with specific engineering example give an improved calculation method. Through example of simulation has proved that using this algorithm can accurately figure out fundamental component and harmonic component, and it has the advantage of algorithm simple and high accuracy [5].

2015 ◽  
Vol 740 ◽  
pp. 364-367
Author(s):  
Su Wang ◽  
Lei Sun ◽  
Wei Cong Huang

Conventionally, the fault signal of motor thermal overload in a non-periodic component is not effectively filtered with Full-wave Fourier Algorithm (or FFA). In this paper, a design which combined Complex Morlet Wavelet Algorithm with Subtraction (or CMWAS) filter is presented. The design gives system model of overload and algorithm analysis It is verified that the new algorithm is better than the FFA algorithm in terms of filtering decaying DC component.


Author(s):  
V. A. Novobritsky ◽  
D. S. Fedosov

THE PURPOSE. This paper considers the problem of relay protection functioning when the current transformer reaches the saturation mode which is provided by transient processes.METHODS. MATLAB Simulink software environment allows reproducing the method of statespace representation by using structural blocks. The model is verified by comparison the time to saturation, obtained by calculation and according to the graphical data of the model. The separation of variables method extracts and graphically displays the investigated components.RESULTS. This paper reveals that applying the requirements of IEC 61869-2:2012 standard, which determines the worst combination of series of unfavorable factors for current transformers in transient mode, can influence a serious impact on the correct operation of relay protection based on current, reactance or differential principle of action. Saturation of the current transformer can lead to both negative results: false operation of relay protection devices and their failure.CONCLUSION. According to the results of the study, it was determined that the presence of a DC component in the primary short-circuit current has the greatest effect on the protection operation. The delays in the restoration of the RMS value of the short-circuit current reached up to 0.3 seconds, which is comparable with the response time of the second protection zones for microprocessor-based relay protection devices. The DC component of the primary current and the presence of residual magnetic induction of the current transformer provides the largest content of the magnetization current, the largest angular error and also the largest content of the second harmonic component in the secondary short-circuit current.


2011 ◽  
Vol 366 ◽  
pp. 286-290
Author(s):  
Li Xin Zhao ◽  
Wei Su ◽  
Liang Sheng Wu

Intelligent release is core control unit of intelligent appliances, which is used to protect power system and power devices from damage under the faults. In this paper, with LPC2478 as Microcontroller, an intelligent release control unit with Ethernet communication functionality was presented. The intelligent release control unit’s basic functions and extended functions were described in brief. Implementation method of control unit was illustrated in detail. Process flow chart for fault diagnosis was supplied. Full-wave Fourier algorithm was adopted to compute fundamental components and harmonic components to filter decaying DC component and non-integer harmonic. This release can be adjusted according to the requirement of power quality to avoid malfunction under the circumstance that non-fault current and voltage fluctuation occur. Furthermore, through Ethernet communication, more functionality can be implemented to make the release more intelligent.


2021 ◽  
pp. 1-13
Author(s):  
Pullabhatla Srikanth ◽  
Chiranjib Koley

In this work, different types of power system faults at various distances have been identified using a novel approach based on Discrete S-Transform clubbed with a Fuzzy decision box. The area under the maximum values of the dilated Gaussian windows in the time-frequency domain has been used as the critical input values to the fuzzy machine. In this work, IEEE-9 and IEEE-14 bus systems have been considered as the test systems for validating the proposed methodology for identification and localization of Power System Faults. The proposed algorithm can identify different power system faults like Asymmetrical Phase Faults, Asymmetrical Ground Faults, and Symmetrical Phase faults, occurring at 20% to 80% of the transmission line. The study reveals that the variation in distance and type of fault creates a change in time-frequency magnitude in a unique pattern. The method can identify and locate the faulted bus with high accuracy in comparison to SVM.


2014 ◽  
Vol 556-562 ◽  
pp. 1510-1514
Author(s):  
Li Qiang Lin ◽  
Hong Wen Yan

For the low efficiency in generating candidate item sets of apriori algorithm, this paper presents a method based on property division to improve generating candidate item sets. Comparing the improved apriori algorithm with the other algorithm and the improved algorithm is applied to the power system accident cases in extreme climate. The experiment results show that the improved algorithm significantly improves the time efficiency of generating candidate item sets. And it can find the association rules among time, space, disasters and fault facilities in the power system accident cases in extreme climate. That is very useful in power system fault analysis.


Energies ◽  
2021 ◽  
Vol 14 (14) ◽  
pp. 4160
Author(s):  
Waqar Uddin ◽  
Tiago D. C. Busarello ◽  
Kamran Zeb ◽  
Muhammad Adil Khan ◽  
Anil Kumar Yedluri ◽  
...  

This paper proposed a control method for output and circulating currents of modular multilevel converter (MMC). The output and circulating current are controlled with the help of arm currents, which contain DC, fundamental frequency, and double frequency components. The arm current is transformed into a stationary reference frame (SRF) to isolate the DC and AC components. The AC component is controlled with a conventional proportional resonant (PR) controller, while the DC component is controlled by a proportional controller. The effective control of the upper arm and lower arm ultimately controls the output current so that it delivers the required power to the grid and circulating current in such a way that the second harmonic component is completely vanished leaving behind only the DC component. Comparative results of leg-level control based on PR controller are included in the paper to show the effectiveness of the proposed control scheme. A three-phase, five-level MMC is developed in MATLAB/Simulink to verify the effectiveness of the proposed control method.