Shunt Petersen-Coil with Resistor for Single Phase Fault Detection in Resonant Grounded Power Distribution Systems
2013 ◽
Vol 860-863
◽
pp. 2007-2012
◽
Keyword(s):
The failure current in resonant grounder power distribution system is small, so it is difficult to detect the fault feeder. This passage presents the equivalent circuit of resonant grounded system, and discusses the difference of electrical characteristics between faulty feeder and sound feeders by using shunt resistors. To reduce the influence of shunt resistors on the system and improve the detection sensitivity, it presents the method of shunting multi-level resistors, and it proves the sensitivity and reliability of this method by EMTP simulation.