Numerical Analysis on Short-Circuit Force Parameters of Windings for Power Transformer

2011 ◽  
Vol 138-139 ◽  
pp. 764-769
Author(s):  
Jian Jun Liu ◽  
Jian Min Wang ◽  
Chong You Jing ◽  
Chang Zai Fan ◽  
Yuan Zhai

The Simplified model of both calculating leakage magnetic field and mechanical force of windings at short circuit condition for a 120MVA/220kV power transformer is set up. The leakage magnetic field ‚ short-circuit force and stress in transformer windings are analyzed and their distributing characteristics are acquired respectively by using FEM. The calculation method and results are validated by withstanding short circuit strength test of the product. A number of useful suggestions are given for design of power transformers.

2014 ◽  
Vol 986-987 ◽  
pp. 1767-1770
Author(s):  
Fang Xu Han ◽  
Yan Li ◽  
Xin Sun ◽  
Longnv Li

The leakage magnetic field and equivalent circuit model of OLTC double-winding power transformer has been established by electromagnetic field Finite Element analysis software. The method of field-circuit coupled method has been used to calculate its magnetic field leakage, the short circuit impedance obtained by the calculation of formula and compared with the experimental data. At the same time, based on the calculation method for the Visual Basic language as a tool for MAGNET software for secondary development, obtain the software to calculate the short-circuit impedance of power transformer simulation software, and is verified by using the typical products, proves the validity of this software.


Author(s):  
Binh Nguyen

Abstract For those attempting fault isolation on computer motherboard power-ground short issues, the optimal technique should utilize existing test equipment available in the debug facility, requiring no specialty equipment as well as needing a minimum of training to use effectively. The test apparatus should be both easy to set up and easy to use. This article describes the signal injection and oscilloscope technique which meets the above requirements. The signal injection and oscilloscope technique is based on the application of Ohm's law in a short-circuit condition. Two experiments were conducted to prove the effectiveness of these techniques. Both experiments simulate a short-circuit condition on the VCC3 power rail of a good working PC motherboard and then apply the signal injection and oscilloscope technique to localize the short. The technique described is a simple, low cost and non-destructive method that helps to find the location of the power-ground short quickly and effectively.


Author(s):  
Antonio R. M. Sousa ◽  
Wellington Da S. Fonseca ◽  
Marcus V. A. Nunes ◽  
Ramon C. F. Araujo ◽  
Diorge de S. Lima

2012 ◽  
Vol 468-471 ◽  
pp. 1086-1089 ◽  
Author(s):  
Yong Ming Xu ◽  
Chao Du ◽  
Da Wei Meng

The problem about the eddy current loss which is caused by leakage magnetic field in ultrahigh pressure large capacity power transformer is becoming more extrusive. It is very significant to research the power transformer leakage magnetic field and eddy current loss on the tank wall thoroughly and accurately. 3D finite element model of power transformer leakage magnetic field and eddy current loss is established in this paper, the eddy current loss on the tank wall is calculated and the distribution is analyzed. For the eddy current loss could be reduced by magnetic shielding, new calculation model are established respectively, then eddy current loss on tank wall could be got with shielding. The best size and location of the shielding could be analyzed after changing the height of the shielding, which provided the important evidence to reduce tank wall eddy current loss effectively. The calculating methods have been proved to be accuracy after experiment.


Energies ◽  
2020 ◽  
Vol 13 (18) ◽  
pp. 4952 ◽  
Author(s):  
Tadeusz Sobczyk ◽  
Marcin Jaraczewski

This paper deals with the problem of the leakage inductance calculations in power transformers. Commonly, the leakage flux in the air zone is represented by short-circuit inductance, which determines the short-circuit voltage, which is a very important factor for power transformers. That inductance is a good representation of the typical power transformer windings, but it is insufficient for multi-winding ones. This paper presents simple formulae for self- and mutual leakage inductance calculations for an arbitrary pair of windings. It follows from a simple 1D approach to analyzing the stray field using a discrete differential operator, and it was verified by the finite element method (FEM) calculation results.


2013 ◽  
Vol 11 (4) ◽  
pp. 692-696
Author(s):  
Yongming Xu ◽  
Dawei Meng ◽  
Chao Du

Author(s):  
Manohar Singh ◽  
Vishnuvarddhan Telukanta ◽  
K S Meera

Abstract Type tests are essential to assess the short circuit withstand capabilities of transformer windings. The mechanical durability of power equipment are checked against the mechanical forces developed during making/breaking short circuit operations. These type tests are generally carried out in indoor transformer test laboratories. Testing of Power Transformer for size more than 200 MVA in 765/400 kV voltage class in an indoor laboratory is not economically feasible. Now a days, power transformer manufacturers are fabricating single phase auto- power transformers of size up to 630 megawatt volt ampere (MVA) rating. Type testing of these transformers in indoor laboratories is not feasible. In view of this, strong short circuit fault feeding capabilities of the national grids can be utilized for type testing of these power transformers in an online manner. However, this may affect the grid operation/control during weak grid operating conditions. Recently, National High Power Testing Laboratory is established for testing of power transformer upto of 630 MVA. This is a unique online transformer test facility for testing of 765/400/220/132 kV class power transformers. An offline simulation has been carried out in this article, to assess the impact of online type testing on the Indian National grid. In this article, an online testing scheme has been presented which enables the national grid operator to analysis the prevailing grid condition & subsequently to decide the safe rating of the power transformer for online testing. The simulated results are cross checked with field results and it is found that simulated results are close to actual field results. The concurrence of simulated and field results helped in successfully commissioning of the testing laboratory.