Thermodynamic analysis of a hybrid membrane liquid desiccant dehumidification and dew point evaporative cooling system

2018 ◽  
Vol 156 ◽  
pp. 440-458 ◽  
Author(s):  
Jie Lin ◽  
Si-Min Huang ◽  
Ruzhu Wang ◽  
Kian Jon Chua
Author(s):  
I Nyoman Suprapta Winaya ◽  
Hendra Wijaksana ◽  
Made Sucipta ◽  
Ainul Ghurri

The high energy consumption of compressor based cooling system has prompted the researchers to study and develop non-compressor based cooling system that less energy consumption, less environment damaging but still has high enough cooling performances. Indirect and semi indirect evaporative cooling system is the feasible non-compressor based cooling systems that can reach the cooling performance required. This two evaporative cooling system has some different in construction, porous material used, airflow scheme and secondary air cooling method used for various applications. This paper would report the cooling performances achieved by those two cooling system in terms of cooling efficiency, cooling capacity, wet bulb effectiveness, dew point effectiveness, and temperature drop. Porous material used in indirect and semi-indirect evaporative cooling would be highlighted in terms of their type, size, thickness and any other feature. The introduction of nanopore skinless bamboo potency as a new porous material for either indirect or semi-indirect evaporative cooling would be described. In the future study of nanopore skinless bamboo, a surface morphology and several hygrothermal test including sorption, water vapor transmission, thermal conductivity test would be applied, before it utilize as a new porous material for direct or semi indirect evaporative cooling.


Author(s):  
Faleh A. Al-Sulaiman ◽  
P. Gandhidasan

This paper presents preliminary findings of the energy analysis of a cooling system with multistage evaporative coolers using liquid desiccant dehumidifier between the stages. The proposed evaporative cooling system utilizes the air humidity for cooling in humid areas and requires no additional water supply. The major energy requirement associated with this cooling system is the energy for regenerating the weak liquid desiccant. In this paper two types of energy namely thermal energy as well as mechanical energy are considered for regeneration. For thermal energy, the heat input for regeneration is supplied from the conventional energy sources such as a simple line heater. Reverse osmosis (RO) process is considered for regeneration by mechanical energy and MFI zeolite membrane is proposed for separation of water from the weak desiccant solution. Energy analysis has been carried out for both methods of regeneration. The results show that the energy consumption is about 25% less for the mechanical regeneration system with 3 % recovery than the thermal energy regeneration system to increase the desiccant solution temperature of 22°C. The COP of the proposed cooling system is defined as the cooling effect by the mass rate of water evaporated in the system divided by the amount of energy supplied to the system, that is, the COP is independent of the energy source.


2016 ◽  
Vol 119 ◽  
pp. 20-27 ◽  
Author(s):  
İlhan Ceylan ◽  
Alper Ergün ◽  
Bahadır Acar ◽  
Mustafa Aydin

Processes ◽  
2021 ◽  
Vol 9 (2) ◽  
pp. 332
Author(s):  
Yuanyuan Zhou ◽  
Zhen Yan ◽  
Ming Gao ◽  
Qiumin Dai ◽  
Yanshun Yu

An indirect evaporative cooling system combining with thermoelectric cooling technology (i.e., TIEC system) is proposed, in which a counter-flow plate-fin indirect evaporative cooler is inserted with thermoelectric cooling (i.e., TEC) modules. In hot and humid climate, condensation may occur on the dry channel surface of the cooler. For the TIEC system, with the aid of TEC technology, the surface temperature of the dry channel can be much lower than that of a traditional indirect evaporative cooler, thus, the condensation from the primary air is more likely to take place. A numerical model of this novel TIEC system is developed with specifically taking condensation from primary air into account. Detailed performance analysis of the TIEC system is carried out. Analytical results found that the condensation from primary air reduces the dew point effectiveness by up to 45.0% by weakening the sensible heat transfer but increases the coefficient of performance by up to 62.2% by increasing the latent heat transfer, under given conditions. The effects of main operating conditions, such as the electrical current I and number n of TEC modules, inlet temperature Tp,i, humidity ratio RHp and velocity Vp of the primary air, and the mass flow rate ratio x of secondary to primary air, are investigated under non-condensation and condensation states. It is shown that condensate is more easily produced under higher I, n, Tp,i, RHp, x and lower Vp.