Transient Dehumidification Characteristics of a Heat Pump in Cooling Mode

1991 ◽  
Vol 113 (4) ◽  
pp. 264-271
Author(s):  
Srinivas Katipamula ◽  
Dennis L. O’Neal

Much of the seasonal cooling operation of the heat pump occurs at part-load conditions when the unit cycles on and off to meet the cooling load. The seasonal efficiency under part-load conditions of the heat pump is typically estimated from a laboratory measurement of the degradation coefficient (CD). Manufacturers are only required to estimate CD at a single test condition where the indoor coil performs sensible cooling only. The effects of transient dehumidification losses are not accounted in estimating the seasonal efficiency. In hot and humid climates, dehumidification performance of a heat pump is as important as the sensible cooling performance. Therefore, a series of tests were designed to quantify the part-load dehumidification characteristics of a three ton residential air-to-air heat pump. The tests include: cycling rates from 0.8 to 10 cycles per hour (cph), percent on-times of 20, 50, and 80 percent, indoor dry-bulb temperature between 22.2°C and 26.7°C, and indoor relative humidity between 20 to 67 percent. The outdoor conditions and the indoor air flow rate were constant for all test runs. All experiments were performed in psychometric chambers under controlled conditions. The dehumidification process started between 60 to 150 seconds after start-up depending on the test conditions. During start-up, the losses in the latent capacity were greater than the losses in the sensible capacity. The dehumidification response increased with indoor dry-bulb temperature at constant relative humidity and decreased with indoor temperature at constant dew-point temperature.

2018 ◽  
Vol 44 ◽  
pp. 00139 ◽  
Author(s):  
Krzysztof Piechurski ◽  
Małgorzata Szulgowska-Zgrzywa ◽  
Jan Danielewicz

Operating in part-load conditions significantly affects the energy efficiency of the air-to-water heat pumps. The currently used method of testing the devices does not provide the necessary data for estimating the degradation of the device’s efficiency in part-load operating mode. The value of the degradation coefficient Cc = 0.9 adopted in accordance with the EN 14825 standard is generally used. However, this value often does not reflect the actual degree of the COP reduction. Hence the new quasi-dynamic model and the calculation approach to the degradation coefficient were proposed. The model reflects the real and overall reduction between the full and part-load COP, not only the energy consumption in the stand-by mode. The estimation was made using the field measurement data of the air-to-water heat pump supplying heat to the low temperature installation. It has been proved that the determination of the main parameter is possible using a relatively small amount of data without losing an accuracy.


2019 ◽  
Vol 2019 ◽  
pp. 1-7 ◽  
Author(s):  
Arun Kumar Shrestha ◽  
Arati Thapa ◽  
Hima Gautam

Monitoring and prediction of the climatic phenomenon are of keen interest in recent years because it has great influence in the lives of people and their environments. This paper is aimed at reporting the variation of daily and monthly solar radiation, air temperature, relative humidity (RH), and dew point over the year of 2013 based on the data obtained from the weather station situated in Damak, Nepal. The result shows that on a clear day, the variation of solar radiation and RH follows the Gaussian function in which the first one has an upward trend and the second one has a downward trend. However, the change in air temperature satisfies the sine function. The dew point temperature shows somewhat complex behavior. Monthly variation of solar radiation, air temperature, and dew point shows a similar pattern, lower at winter and higher in summer. Maximum solar radiation (331 Wm-2) was observed in May and minimum (170 Wm-2) in December. Air temperature and dew point had the highest value from June to September nearly at 29°C and 25°C, respectively. The lowest value of the relative humidity (55.4%) in April indicates the driest month of the year. Dew point was also calculated from the actual readings of air temperature and relative humidity using the online calculator, and the calculated value showed the exact linear relationship with the observed value. The diurnal and nocturnal temperature of each month showed that temperature difference was relatively lower (less than 10°C) at summer rather than in winter.


Author(s):  
Bowen Ding ◽  
Liping Xu ◽  
Jiandao Yang ◽  
Rui Yang ◽  
Yuejin Dai

Modern large steam turbines for power generation are required to operate much more flexibly than ever before, due to the increasing use of intermittent renewable energy sources such as solar and wind. This has posed great challenges to the design of LP steam turbine exhaust systems, which are critical to recovering the leaving energy that is otherwise lost. In previous studies, the design had been focused on the exhaust diffuser with or without the collector. Although the interaction between the last stage and the exhaust hood has been identified for a long time, little attention has been paid to the last stage blading in the exhaust system’s design process, when the machine frequently operates at part-load conditions. This study focuses on the design of LP exhaust systems considering both the last stage and the exhaust diffuser, over a wide operating range. A 1/10th scale air test rig was built to validate the CFD tool for flow conditions representative of an actual machine at part-load conditions, characterised by highly swirling flows entering the diffuser. A numerical parametric study was performed to investigate the effect of both the diffuser geometry variation and restaggering the last stage rotor blades. Restaggering the rotor blades was found to be an effective way to control the level of leaving energy, as well as the flow conditions at the diffuser inlet, which influence the diffuser’s capability to recover the leaving energy. The benefits from diffuser resizing and rotor blade restaggering were shown to be relatively independent of each other, which suggests the two components can be designed separately. Last, the potentials of performance improvement by considering both the last stage rotor restaggering and the diffuser resizing were demonstrated by an exemplary design, which predicted an increase in the last stage power output of at least 1.5% for a typical 1000MW plant that mostly operates at part-load conditions.


Sign in / Sign up

Export Citation Format

Share Document