A Comparison of Detailed and Simple Building Energy Analysis Tools for Eco–Friendly Office Building Design

2012 ◽  
Vol 178-181 ◽  
pp. 3-6
Author(s):  
Sang Tae No ◽  
Jae Yeob Kim

The main objective of this study is to present low energy building and design process using building energy analysis tools, designing a practical office building. EnergyPlus and ECO2 were selected as primary and second tools. The peak heating and cooling load of the designed office building were simulated by EnergyPlus. And the peak load values were applied to ECO2 as HVAC and plant system's capacity. The second objective of this study is to investigate the tendency of simulation results by ECO2 using various input parameters, because ECO2 is a newly proposed energy rating tool for office building by KICT. The passive and active parameters were selected, such as U-factor, shading, orientation, system capacity, and so on. The primary energy usages were calculated by ECO2 and the results and their tendency were analyzed.

Author(s):  
Patrick H. Oosthuizen ◽  
Marilyn Lightstone

Energy simulation (ES) computer programs have been and still are widely used in the design and analysis of building energy systems. However, most ES programs assume that the air in the indoor building space is well mixed. As a result such programs cannot accurately predict building energy consumption for buildings with non-uniform air temperature distributions in the indoor space. They also cannot predict variations in thermal comfort levels in different parts of the building. Computational Fluid Dynamics (CFD), as a result, has become quite widely used in the design and evaluation of buildings energy systems in recent years. CFD can be used, for example, to predict the thermal comfort, natural lighting, natural ventilation, spread of smoke and contaminants in the building, and indoor air quality in a building. As a result it is proving to be an extremely valuable tool in the design of buildings and building systems. This, together with the fact that today’s commercial CFD software packages are relatively easy to use, has led to this quite widespread adoption of CFD methods in building energy analysis. Energy usage in buildings can be decreased by, for example, the use of daylighting (use of solar illumination in place of artificial lighting), by the use of natural ventilation, and by solar heating. CFD analysis provides a means of relatively accurately studying the effect of building design on the effectiveness of daylighting, natural ventilation, and solar heating. Another example of the use of CFD is in the study of the effect of various window blind arrangements on the building performance. In order for a CFD package to be used effectively in building energy analysis it should allow the use of a wide range of turbulence models, it should allow the incident solar radiation on the building to be found and used in the calculation of the indoor flow and temperature fields, it should allow the radiant heat exchange in the building to be incorporated into the calculation, and it should allow the effects of the thermal masses of the walls, floors, etc. to be easily incorporated into the calculation when they are deemed to be important. In this paper, the use of CFD methods in building energy analysis will be discussed as will some applications of CFD in building design. The use of CFD methods in developing design guidelines for particular types of buildings will also be briefly discussed.


Energies ◽  
2021 ◽  
Vol 14 (4) ◽  
pp. 1080
Author(s):  
Mamdooh Alwetaishi ◽  
Omrane Benjeddou

The concern regarding local responsive building design has gained more attention globally as of late. This is due to the issue of the rapid increase in energy consumption in buildings for the purpose of heating and cooling. This has become a crucial issue in educational buildings and especially in schools. The major issue in school buildings in Saudi Arabia is that they are a form of prototype school building design (PSBD). As a result, if there is any concern in the design stage and in relation to the selection of building materials, this will spread throughout the region. In addition to that, the design is repeated regardless of the climate variation within the kingdom of Saudi Arabia. This research will focus on the influence of the window to wall ratio on the energy load in various orientations and different climatic regions. The research will use the energy computer tool TAS Environmental Design Solution Limited (EDSL) to calculate the energy load as well as solar gain. During the visit to the sample schools, a globe thermometer will be used to monitor the globe temperature in the classrooms. This research introduces a framework to assist architects and engineers in selecting the proper window to wall ratio (WWR) in each direction within the same building based on adequate natural light with a minimum reliance on energy load. For ultimate WWR for energy performance and daylight, the WWR should range from 20% to 30%, depending on orientation, in order to provide the optimal daylight factor combined with building energy efficiency. This ratio can be slightly greater in higher altitude locations.


2016 ◽  
Vol 68 ◽  
pp. 183-193 ◽  
Author(s):  
Hyunjoo Kim ◽  
Zhenhua Shen ◽  
Inhan Kim ◽  
Karam Kim ◽  