scholarly journals Performance Analysis of a Deep Vertical Closed-Loop Heat Exchanger through Thermal Response Test and Thermal Resistance Analysis

2016 ◽  
Vol 49 (6) ◽  
pp. 459-467
Author(s):  
Byoung Ohan Shim ◽  
Chan-Hee Park ◽  
Heuy-Nam Cho ◽  
Byeong-Dae Lee ◽  
Yujin Nam
2019 ◽  
Vol 27 (02) ◽  
pp. 1950015 ◽  
Author(s):  
Keun Sun Chang ◽  
Young Jae Kim ◽  
Min Jun Kim

The standing column well (SCW) for ground source heat pump (GSHP) systems is a highly promising technology with its high heat capacity and efficiency. In this study, a large-scale thermal response tester has been built, which is capable of imposing a wide range of heat on the SCW ground heat exchangers and measuring time responses of their thermal parameters. Two standing column wells in one site but with different well hydrological and geological conditions are tested to study their effects on the thermal performances. Borehole thermal resistance ([Formula: see text]) and the effective thermal conductivity ([Formula: see text]) are derived from data obtained from the thermal response test (TRT) by using a line source method. Results show that the influence of groundwater movement on the thermal conductivity of the SCW is not very significant (3.6% difference between two different geological conditions). This indicates that results of one TRT measurement can be applied to other SCWs in the same site, with which considerable time and cost are saved. The increase of circulation flow rate enhances the ground thermal conductivity moderately (4.5% increase with flow rate increase of 45%), but the borehole thermal resistance is substantially lowered (about 25.9%).


2014 ◽  
Vol 937 ◽  
pp. 381-385
Author(s):  
Yi Liu ◽  
Yang Shi ◽  
Ya Ning Zhang

Abstract. A thermal response test (TRT) apparatus is introduced in this paper for determination of the performance of underground heat exchanger in ground-source heat pump system. The inlet and outlet temperatures of the underground heat exchanger can be real-time tested to obtain the heat transfer data. The apparatus was used to test a underground heat exchanger for its inlet and outlet temperatures in Red Star farm, Beian City, Heilongjiang province, China. The inlet and outlet temperatures varied in the ranges of 10.62~13.57°C and 9.01~11.88°C within 24 hours, respectively.


Energies ◽  
2019 ◽  
Vol 12 (4) ◽  
pp. 651 ◽  
Author(s):  
Sang Bae ◽  
Yujin Nam ◽  
Jong Choi ◽  
Kwang Lee ◽  
Jae Choi

A ground source heat pump (GSHP) system has higher performance than air source heat pump system due to the use of more efficient ground heat source. However, the GSHP system performance depends on ground thermal properties and groundwater conditions. There are many studies on the improvement of GSHP system by developing ground heat exchanger (GHX) and heat exchange method. Several studies have suggested methods to improve heat exchange rate for the development of GHX. However, few real-scale experimental studies have quantitatively analyzed their performance using the same ground conditions. Therefore, the objective of this study was to evaluate the thermal performance of various pipe types of GHX by the thermal response test (TRT) under the same field and test conditions. Four kinds of GHX (HDPE type, HDPE-nano type, spiral fin type, and coaxial type) were constructed in the same site. Inlet and outlet temperatures of GHXs and effective thermal conductivity were measured through the TRT. In addition, the borehole thermal resistance was calculated to comparatively analyze the correlation of the heat exchange performance with each GHX. Result of the TRT revealed that averages effective thermal conductivities of HDPE type, HDPE-nano, spiral fin type, and coaxial type GHX were 2.25 W/m·K, 2.34 W/m·K, 2.55 W/m·K, and 2.16 W/m·K, respectively. In the result, it was found that the average borehole thermal resistance can be an important factor in TRT, but the effect of increased thermal conductivity of pipe material itself was not significant.