scholarly journals Pengaruh Kecepatan Fluida Dan Jarakantar Zig Zag Filter Foam Filler Terhadap Efektifitas Cooling Tower

2021 ◽  
Vol 6 (1) ◽  
pp. 27-32
Author(s):  
Andrea Setiawan ◽  
A’rasy Fahruddin

The purpose of this study was to determine the effect of fluid velocity and the distance between zig zagfilters on the cooling tower by varying the distance between zig zag foam bio filters. In this study using bio filterfoam material in the form of zig zg by using wire mesh where the tested distance is 5cm, 10cm, and also 15cm. Thenthe water is heated using a heater until it reaches a temperature of 40ºC and then the water is flowed up with a pipeusing a pump and released using a nozzle, then the hot water will go down to the reservoir by passing the bio filterfoam filter that has been installed with a distance of 5cm , 10cm and 15cm. Where there is also a disposal valve thatis done that is closed and faucets are also open ½ and fully open. Good cooling value is indicated by good results oncooling or also cooling faster which is 5cm which results in an average cooling value of 36.53 ºC when the exhaustvalve is fully open, while the value is not good or less optimal cooling it is shown when the drain valve is closed at azig zag distance of 10cm and also 15cm which yields 37.60 ºC data at a zig zag distance of 15cm.

2009 ◽  
Vol 13 (4) ◽  
pp. 91-98
Author(s):  
Elazm Abo ◽  
Farouk Elsafty

The main objective of this study is to find a proper solution for the cross-flow water cooling tower problem, also to find an empirical correlation's controlling heat and mass transfer coefficients as functions of inlet parameters to the tower. This is achieved by constructing an experimental rig and a computer program. The computer simulation solves the problem numerically. The apparatus used in this study comprises a cross-flow cooling tower. From the results obtained, the 'characteristic curve' of cross-flow cooling towers was constructed. This curve is very helpful for designers in order to find the actual value of the number of transfer units, if the values of inlet water temperature or inlet air wet bulb temperature are changed. Also an empirical correlation was conducted to obtain the required number of transfer units of the tower in hot water operation. Another correlation was found to obtain the effectiveness in the wet bulb operation.


2020 ◽  
Vol 170 ◽  
pp. 01009
Author(s):  
Akshay S. Dhurandhar ◽  
Amarsingh B. Kanase-Patil

Cooling tower is an indispensable part, used as a direct contact type heat exchanger mainly for evaporative cooling. Cooling tower generally dissipates, remove heat from thermal power plants. In an induced draft cooling tower of counter flow, used for a mini-steam power plant, hot water enters at the top, while the air is introduced at the bottom and exits at the top, air is allowed to come in contact with falling water droplets, causing evaporative cooling. A possibility of desired change with different spray angle, patterns, is tried and analysed. On findings, best suited spray nozzle angle resulted is 90°, and amongst three spray patterns, full cone, hollow cone and spiral type nozzle; full cone nozzle of 90° spray angle helps achieving efficiency up to 82%. The range increases successively from 9.8°C to 15.5°C for FC nozzle, in approach to WBT; the desirable fall of 3.56°C is attained with effectiveness of 81.63%.


2006 ◽  
Vol 73 (5) ◽  
pp. 1452-1456 ◽  
Author(s):  
Diaraf Farba Yaradou ◽  
Sylvie Hallier-Soulier ◽  
Sophie Moreau ◽  
Florence Poty ◽  
Yves Hillion ◽  
...  

ABSTRACT We evaluated a ready-to-use real-time quantitative Legionella pneumophila PCR assay system by testing 136 hot-water-system samples collected from 55 sites as well as 49 cooling tower samples collected from 20 different sites, in parallel with the standard culture method. The PCR assay was reproducible and suitable for routine quantification of L. pneumophila. An acceptable correlation between PCR and culture results was obtained for sanitary hot-water samples but not for cooling tower samples. We also monitored the same L. pneumophila-contaminated cooling tower for 13 months by analyzing 104 serial samples. The culture and PCR results were extremely variable over time, but the curves were similar. The differences between the PCR and culture results did not change over time and were not affected by regular biocide treatment. This ready-to-use PCR assay for L. pneumophila quantification could permit more timely disinfection of cooling towers.


2006 ◽  
Vol 72 (4) ◽  
pp. 2801-2808 ◽  
Author(s):  
Philippe Joly ◽  
Pierre-Alain Falconnet ◽  
Janine André ◽  
Nicole Weill ◽  
Monique Reyrolle ◽  
...  

ABSTRACT Quantitative Legionella PCRs targeting the 16S rRNA gene (specific for the genus Legionella) and the mip gene (specific for the species Legionella pneumophila) were applied to a total of 223 hot water system samples (131 in one laboratory and 92 in another laboratory) and 37 cooling tower samples (all in the same laboratory). The PCR results were compared with those of conventional culture. 16S rRNA gene PCR results were nonquantifiable for 2.8% of cooling tower samples and up to 39.1% of hot water system samples, and this was highly predictive of Legionella CFU counts below 250/liter. PCR cutoff values for identifying hot water system samples containing >103 CFU/liter legionellae were determined separately in each laboratory. The cutoffs differed widely between the laboratories and had sensitivities from 87.7 to 92.9% and specificities from 77.3 to 96.5%. The best specificity was obtained with mip PCR. PCR cutoffs could not be determined for cooling tower samples, as the results were highly variable and often high for culture-negative samples. Thus, quantitative Legionella PCR appears to be applicable to samples from hot water systems, but the positivity cutoff has to be determined in each laboratory.


2018 ◽  
Author(s):  
Dessy Agustina Sari

Indicator overheat on robot transformer of spot welding was gun thermos alarm. Thermostat which adheringin the machine could be shut down the robot if this component detected the excessive warm below the standard operation. Impurities (scale, and deposit) existence caused heat transfer process disturbed, exchanged thermal between cold and hot water. This research methods were replacement part filler of the cooling tower and flushing the pipeline by chemical. The result showed a step progressing which cooling water reached the standard temperature, 30oC. Performance spot welding was being better so time production worked normally.


Author(s):  
Abdolreza Zaltash ◽  
Andrei Petrov ◽  
Randall Linkous ◽  
Edward Vineyard ◽  
David Goodnack ◽  
...  

During the summer months, air-conditioning (cooling) is the single largest use of electricity in both residential and commercial buildings with the major impact on peak electric demand. Improved air-conditioning technology has by far the greatest potential impact on the electric industry compared to any other technology that uses electricity. Thermally activated absorption air-conditioning (absorption chillers) can provide overall peak load reduction and electric grid relief for summer peak demand. This paper describes an innovative absorption technology based on integrated rotating heat exchangers to enhance heat and mass transfer resulting in a potential reduction of size, cost, and weight of the “next generation” absorption units. This absorption chiller (RAC) is a 4.5 kW (1.3 refrigeration tons or RT) air-cooled lithium bromide (LiBr)/water unit powered by hot water generated using the solar energy and/or waste heat. Typically LiBr/water absorption chillers are water-cooled units which use a cooling tower to reject heat. Cooling towers require a large amount of space and increase start-up and maintenance costs. However, RAC is an air-cooled absorption chiller which requires no cooling tower. The purpose of this evaluation is to verify RAC performance by comparing the Coefficient of Performance (COP or ratio of cooling capacity to thermal energy input) and the cooling capacity results with those of the manufacturer. The performance of the RAC was tested at Oak Ridge National Laboratory (ORNL) in a controlled environment at various hot and chilled water flow rates, air handler flow rates, and ambient temperatures. Temperature probes, mass flow meters, rotational speed measuring device, pressure transducers, and a web camera mounted inside the unit were used to monitor the RAC via a web control-based data acquisition system using Automated Logic Controller (ALC). Results showed a COP and cooling capacity of approximately 0.58 and 3.7 kW respectively at 35°C (95°F) design condition for ambient temperature with 40°C (104°F) cooling water temperature. This is in close agreement with the manufacturer data of 0.60 for COP and 3.9 kW for cooling capacity. Future work will use these performance results to evaluate the potential benefits of rotating heat exchangers in making the “next-generation” absorption chillers more compact and cost effective without any significant degradation in the performance. Future studies will also evaluate the feasibility of using rotating heat exchangers in other applications.


Energies ◽  
2021 ◽  
Vol 14 (19) ◽  
pp. 6203
Author(s):  
Tabish Alam ◽  
Nagesh Babu Balam ◽  
Kishor Sitaram Kulkarni ◽  
Md Irfanul Haque Siddiqui ◽  
Nishant Raj Kapoor ◽  
...  

The need for hot water in residential buildings requires a significant energy potential. Therefore, an efficient water heating system is important to achieve the goal of saving high-grade energy. The most simple and cheapest solar water heater is a flat plate solar collector (FPSC), which can increase the thermal energy of fluid by absorbing solar radiation. The performance of FPSC is comparatively low due to the dilute nature of solar insolation. Therefore, advancement of FPSC is being undertaken to improve the performance and achieve size reduction. In past, several techniques have been exploited to improve the performance of FPSC, which are presented in the present paper. These techniques include surface modifications, use of nanofluids, solar selective coating, and applications of a mini/macro channel, heat pipe, and vacuum around absorber. Surface modification on the absorber/absorber tube techniques are exploited to transfer the maximum possible solar energy to working fluids by increasing the heat transfer rate. Insertion of wire mesh, coil, and twisted tapes in the flow has great potential to increase the Nusselt number by 460% at the expense of a large pressure drop. Selective coating of Cu0.44 Ti0.44 Mn0.84 helps to absorb up to 97.4% of the incident solar energy, which is more significant. Many nanofluids have been exploited as heat transfer fluids, as they not only increase the performance but also reduce the fluid inventory. So, these techniques play a very prominent role in the performance of FPSC, which are discussed in detail. Summaries of the results are presented and recommendations proposed.


2020 ◽  
Author(s):  
Emilie Bédard ◽  
Hana Trigui ◽  
Jeffrey Liang ◽  
Margot Doberva ◽  
Kiran Paranjape ◽  
...  

AbstractIn large-building water systems, Legionella pneumophila is exposed to common environmental stressors such as copper. The aim of this study was to evaluate the susceptibility to copper of L. pneumophila isolates recovered from various sites: two clinical and seven environmental from hot water systems biofilm & water, and from cooling tower water. After one-week acclimation in simulated drinking water, strains were exposed to various copper concentrations (0.8 to 5 mg/L) for over 672 hours. Complete loss of culturability was observed for three isolates, following copper exposure to 5 mg/L for 672h. Two ST1427-like isolates were highly sensitive to copper, while the other two, isolated from biofilm samples, were resistant. The expression of the copper resistance gene copA evaluated by RT-qPCR was significantly higher for the biofilm isolates. All four ST1427-like isolates were recovered from the same water system during an outbreak. Whole genome sequencing results confirmed that the four isolates are very close phylogenetically, differing by only 29 single nucleotide polymorphisms, suggesting in situ adaptation to microenvironmental conditions, possibly due to epigenetic regulation. These results indicate that the immediate environment within a building water distribution system influences the tolerance of L. pneumophila to copper. Increased contact of L. pneumophila biofilm strains with copper piping or copper alloys in the heat exchanger might lead to local adaptation. The phenotypic differences observed between water and biofilm isolates from the hot water system of a healthcare facility warrants further investigation to assess the relevance of evaluating disinfection performances based on water sampling alone.ImportanceLegionella pneumophila is a pathogen indigenous to natural and large building water systems in the bulk and the biofilm phases. The immediate environment within a system can impact the tolerance of L. pneumophila to environmental stressors, including copper. In healthcare facilities, copper levels in water can vary, depending on water quality, plumbing materials and age. This study evaluated the impact of the isolation site (water vs biofilm, hot water system vs cooling tower) within building water systems. Closely related strains isolated from a healthcare facility hot water system exhibited variable tolerance to copper stress shown by differential expression of copA, with biofilm isolates displaying highest expression and tolerance. Relying on the detection of L. pneumophila in water samples following exposure to environmental stressor such as copper may underestimate the prevalence of L. pneumophila, leading to inappropriate risk management strategies and increasing the risk of exposure for vulnerable patients.


Sign in / Sign up

Export Citation Format

Share Document