Effect of Wind Directions on the Thermal Performance of Three Aligned NDDCT: Parallel and Perpendicular Directions

2012 ◽  
Vol 232 ◽  
pp. 218-222
Author(s):  
Samad Ghafarigousheh ◽  
Ali Akbar Golneshan

In this paper a 3-D numerical model is used to investigate the thermal performance of a three aligned unit of NDDCT under crosswind condition. The computed results show that, there are major differences in computed velocity patterns and pressure fields around the cooling tower due to neighboring of a number of cooling towers will result considerable changes in computed flow parameters hence; the thermal performance losses for the single tower under crosswind are superior to those when this towers are incorporated in aligned arrangement. Results also show that the best thermal performance of the three aligned NDDCT is achieved when the crosswind is directed along the towers connection line.

Author(s):  
Mostafa H. Sharqawy ◽  
John H. Lienhard ◽  
Syed M. Zubair

Seawater cooling towers have been used since the 1970’s in power generation and other industries, so as to reduce the consumption of freshwater. The salts in seawater are known to create a number of operational problems including salt deposition, packing blockage, corrosion, and certain environmental impacts from salt drift and blowdown return. In addition, the salinity of seawater affects the thermophysical properties which govern the thermal performance of cooling towers, including vapor pressure, density, specific heat, viscosity, thermal conductivity and surface tension. In this paper, the thermal performance of seawater cooling towers is investigated using a detailed model of a counterflow wet cooling tower. The model takes into consideration the coupled heat and mass transfer processes and does not make any of the conventional Merkel approximations. In addition, the model incorporates the most up-to-date seawater properties in the literature. The model governing equations are solved numerically and its validity is checked by data in the literature. Based on the results of the model, a correction factor is obtained which characterizes the degradation of the cooling tower effectiveness when seawater is used.


Author(s):  
Mostafa H. Sharqawy ◽  
John H. Lienhard ◽  
Syed M. Zubair

Seawater cooling towers have been used since the 1970s in power generation and other industries, so as to reduce the consumption of freshwater. The salts in seawater are known to create a number of operational problems, including salt deposition, packing blockage, corrosion, and certain environmental impacts from salt drift and blowdown return. In addition, the salinity of seawater affects the thermophysical properties that govern the thermal performance of cooling towers, including vapor pressure, density, specific heat, viscosity, thermal conductivity, and surface tension. In this paper, the thermal performance of seawater cooling towers is investigated using a detailed model of a counterflow wet cooling tower. The model takes into consideration the coupled heat and mass transfer processes and does not make any of the conventional Merkel approximations. In addition, the model incorporates the most up-to-date seawater properties in the literature. The model governing equations are solved numerically, and its validity is checked against the available data in the literature. Based on the results of the model, a correction factor that characterizes the degradation of the cooling tower effectiveness as a function of seawater salinity and temperature approach is presented for performance evaluation purposes.


2020 ◽  
Vol 329 ◽  
pp. 03007
Author(s):  
Ilnur Madyshev ◽  
Ildar Sabanaev ◽  
Vitaly Kharkov ◽  
Lenar Ganiev ◽  
Andrey Dmitriev

Biofouling can significantly deteriorate the efficiency of cooling towers. A cooling tower with a three-flow cooling circuit has been developed. The fill pack consists of inclined-corrugated contact elements with perforation. One of the advantages of the proposed cooling tower is the possibility of uniform distribution of liquid over the cross-sectional area. The paper represents the results of an experimental study of the thermal performance of the three-flow cooling tower. It was found that when the wetting rate of the liquid increases, the thermal performance of the cooling tower can reach 47.8%. The developed three-flow cooling tower allows excluding the propagation of microorganisms and reducing the biofouling of industrial water systems along with the high performance for circulating water.


2017 ◽  
Vol 21 (6 Part A) ◽  
pp. 2491-2501 ◽  
Author(s):  
Qian Wang ◽  
Pei-Hong Wang ◽  
Zhi-Gang Su

This paper proposes an analytical model for simultaneous heat and mass transfer processes in a counter flow wet cooling tower, with the assumption that the enthalpy of the saturated air is a linear function of the water surface temperature. The performance of the proposed analytical model is validated in some typical cases. The validation reveals that, when cooling range is in a certain interval, the proposed model is not only comparable with the accurate model, but also can reduce computational complexity. In addition, with the proposed analytical model, the thermal performance of the counter flow wet cooling towers in power plants is calculated. The results show that the proposed analytical model can be applied to evaluate and predict the thermal performance of counter flow wet cooling towers.


2020 ◽  
Vol 68 (2) ◽  
pp. 137-145
Author(s):  
Yang Zhouo ◽  
Ming Gao ◽  
Suoying He ◽  
Yuetao Shi ◽  
Fengzhong Sun

Based on the basic theory of water droplets impact noise, the generation mechanism and calculation model of the water-splashing noise for natural draft wet cooling towers were established in this study, and then by means of the custom software, the water-splashing noise was studied under different water droplet diameters and water-spraying densities as well as partition water distribution patterns conditions. Comparedwith the water-splashing noise of the field test, the average difference of the theoretical and the measured value is 0.82 dB, which validates the accuracy of the established theoretical model. The results based on theoretical model showed that, when the water droplet diameters are smaller in cooling tower, the attenuation of total sound pressure level of the water-splashing noise is greater. From 0 m to 8 m away from the cooling tower, the sound pressure level of the watersplashing noise of 3 mm and 6 mm water droplets decreases by 8.20 dB and 4.36 dB, respectively. Additionally, when the water-spraying density becomes twice of the designed value, the sound pressure level of water-splashing noise all increases by 3.01 dB for the cooling towers of 300 MW, 600 MW and 1000 MW units. Finally, under the partition water distribution patterns, the change of the sound pressure level is small. For the R s/2 and Rs/3 partition radius (Rs is the radius of water-spraying area), when the water-spraying density ratio between the outer and inner zone increases from 1 to 3, the sound pressure level of water-splashing noise increases by 0.7 dB and 0.3 dB, respectively.


Author(s):  
Shuo Li ◽  
M. R. Flynn

AbstractVisible plumes above wet cooling towers are of great concern due to the associated aesthetic and environmental impacts. The parallel path wet/dry cooling tower is one of the most commonly used approaches for plume abatement, however, the associated capital cost is usually high due to the addition of the dry coils. Recently, passive technologies, which make use of free solar energy or the latent heat of the hot, moist air rising through the cooling tower fill, have been proposed to minimize or abate the visible plume and/or conserve water. In this review, we contrast established versus novel technologies and give a perspective on the relative merits and demerits of each. Of course, no assessment of the severity of a visible plume can be made without first understanding its atmospheric trajectory. To this end, numerous attempts, being either theoretical or numerical or experimental, have been proposed to predict plume behavior in atmospheres that are either uniform versus density-stratified or still versus windy (whether highly-turbulent or not). Problems of particular interests are plume rise/deflection, condensation and drift deposition, the latter consideration being a concern of public health due to the possible transport and spread of Legionella bacteria.


Author(s):  
B E A Fisher

An assessment of the effects of visible cooling tower plumes on the local environment can be a necessary part of any proposal for a new large industrial process. Predictions of the dispersion of plumes from cooling towers are based on methods developed for chimney emissions. However, the kinds of criteria used to judge the acceptability of cooling tower plumes are different from those used for stack plumes. The frequency of long elevated plumes and the frequency of ground fogging are the two main issues. It is shown that events associated with significant plume visibility are dependent both on the operating characteristics of the tower and on the occurrence of certain meteorological conditions. The dependence on atmospheric conditions is shown to be fairly complex and simple performance criteria based on the exit conditions from the tower are not sufficient for assessments.


1989 ◽  
Vol 111 (4) ◽  
pp. 837-843 ◽  
Author(s):  
H. Jaber ◽  
R. L. Webb

This paper develops the effectiveness-NTU design method for cooling towers. The definitions for effectiveness and NTU are totally consistent with the fundamental definitions used in heat exchanger design. Sample calculations are presented for counter and crossflow cooling towers. Using the proper definitions, a person competent in heat exchanger design can easily use the same basic method to design a cooling tower of counter, cross, or parallel flow configuration. The problems associated with the curvature of the saturated air enthalpy line are also treated. A “one-increment” design ignores the effect of this curvature. Increased precision can be obtained by dividing the cooling range into two or more increments. The standard effectiveness-NTU method is then used for each of the increments. Calculations are presented to define the error associated with different numbers of increments. This defines the number of increments required to attain a desired degree of precision. The authors also summarize the LMED method introduced by Berman, and show that this is totally consistent with the effectiveness-NTU method. Hence, using proper and consistent terms, heat exchanger designers are shown how to use either the standard LMED or effectiveness-NTU design methods to design cooling towers.