Thermal Performance Comparison for Five Liquid Heat Sink Designs

Author(s):  
Christopher Greene ◽  
Randall D. Manteufel ◽  
Amir Karimi

Five high-flow liquid-cooled heat sink designs are compared for the cooling of a single chip CPU. Five distinctive design configurations are considered with regard to the introduction, passage, and extraction of cooling fluid. The typical water flow rate is about 3.8 liters per minute (lpm) with flow passages in the primary heat transfer area ranging from 2 to 0.1mm. The design configurations are summarized and compared, considering: the primary convective heat transfer area, flow passage streamlining, acceleration mechanisms, and nominal fluid velocity in the primary heat transfer area. Overall pressure drop and thermal resistance are compared for varying flow rates of water. At the nominal flow, the pressure drops ranged from 1 kPa to 20 kPa. In the restrictive designs, such as nozzles, flow acceleration accounts for the largest source of pressure drop. In some designs, a large fraction of the overall pressure drop is due to circuitous flow associated with the introduction and/or extraction of flow which contributes little to heat removal. At the nominal flow, the overall thermal resistance varied from 0.14 to 0.18 C/W. As flow rate increases the overall thermal resistance decreases. Results indicated that 80 to 85% of the total thermal resistance is due to conduction and about 15 to 20% attributed to convection at the nominal flow rate. There is minimal thermal benefit for flow rates beyond twice the nominal while this substantially increases fluid pumping requirements. This study highlights design features which yield above average heat transfer performance with minimal pressure drop for high-flow liquid-cooled heat sinks.

Author(s):  
Ildar F. Akhmadullin ◽  
Randall D. Manteufel ◽  
Christopher Greene

Experimental measurements are reported for high-flow liquid-cooled heat sinks designed for cooling electronics components such as a CPU. The flow rate is up to 2 GPM with internal flow passage length scales on the order of 0.1 to 1.0 mm in the primary heat transfer region. Of the designs tested, three achieved maximum flow rates with pressure drops of less than 1.5 psi. Two have lower maximum flow rates because of higher internal flow resistance. In the experiments, particular attention is given to sources of experimental uncertainty and the propagation of uncertainty through the calculations to reported thermal resistance, R (°C/W). Analysis includes bias and precision errors for direct measurement of temperature, flow rate, and pressure drop. Additionally, a separate thermocouple calibration test is reported to establish measurement uncertainties for the system. Main emphasis is made to the error propagation in thermal resistance calculations of each heat sink and measurement of heat removal rate from the CPU. Data is used to determine the standard error for R which ranges up to about 0.05 °C/W with the maximum for one heat sink up to 0.07 °C/W. Averaging of repeated measurements at the same flow rate without accounting for the range of the original data will result in lower uncertainties in the reported results.


Author(s):  
T. J. John ◽  
B. Mathew ◽  
H. Hegab

The need for dissipating heat from microsystems has increased drastically in the last decade. Several methods of heat dissipation using air and liquids have been proposed by many studies, and pin-fin micro heat sinks are one among them. Researchers have developed several effective pin-fin structures for use in heat sinks, but not much effort has been taken towards the optimization of profile and dimensions of the pin-fin. In this paper the authors studied the effect of different pin-fin shapes on the thermal resistance and pressure drop in a specific micro heat-sink. Optimization subjected to two different constraints is studied in this paper. The first optimization is subjected to constant flow rate and the second one is subjected to constant pressure drop. Both optimization processes are carried out using computer simulations generated using COVENTORWARE™. Two of the best structures from each of these optimization studies are selected and further analysis is performed for optimizing their structure dimensions such as width, height and length. A section of the total micro heat-sink is modeled for the initial optimization of the pin-fin shape. The model consists of two sections, the substrate and the fluid. Six different shapes: square, circle, rectangle, triangle, oval and rhombus were analyzed in the initial optimization study. Preliminary tests were conducted using the first model described above for a flow rate of 0.6ml/min. The non dimensional overall thermal resistance of the heat sink, and the nondimensional pumping power was calculated from the results. A figure of merit (FOM) was developed using the nondimensional thermal resistance and nondimensional pumping power for each structure with different pin-fin shapes. Smaller the value of FOM better the performance of the heat sink. The study revealed that the circle and ellipse structures have the best performance and the rectangle structure had the worst performance at low flow rates. At high flow rates rectangular and square structures have the best performance.


2015 ◽  
Vol 1105 ◽  
pp. 253-258 ◽  
Author(s):  
Weerapun Duangthongsuk ◽  
Somchai Wongwises

This research presents an experimental investigation on the heat transfer performance and pressure drop characteristics of a heat sink with miniature square pin fin structure using nanofluids as coolant. ZnO-water nanofluids with particle concentrations of 0.2, 0.4 and 0.6 vol.% are used as working fluid and then compared with the data for water-cooled heat sink. Heat sink made from aluminum material with dimension around 28 x 33 x 25 mm (width x length x thickness). The heat transfer area and hydraulic diameter of the each flow channel is designed at 1,565 mm2and 1.2 mm respectively. Uniform heat flux at the bottom of heat sink is achieved using an electric heater. The experimental data illustrate that the thermal performance of heat sink using nanofluids as coolant is average 14% higher than that of the water-cooled heat sink. For pressure drop, the data show that the pressure drop of nanofluids is a few percent larger than that of the water-cooled heat sink.


2020 ◽  
pp. 0958305X2094531
Author(s):  
Hebert Lugo-Granados ◽  
Lázaro Canizalez-Dávalos ◽  
Martín Picón-Núñez

The aim of this paper is to develop guidelines for the placing of new coolers in cooling systems subject to retrofit. The effects of the accumulation of scale on the flow system are considered. A methodology to assess the interconnected effect of local fluid velocity and fouling deposition is developed. The local average fluid velocity depends on the water flow rate distribution across the piping network. The methodology has four main calculation components: a) the determination of the flow rate distribution across the piping network, b) the prediction of fouling deposition, c) determination of the hydraulic changes and the effect on fouling brought about by the placing of new exchangers into an existing structure, and d) the calculation of the total cooling load and pressure drop of the system. The set of disturbances introduced to the system through fouling and the incorporation of new coolers, create network responses that eventually influence the cooling capacity and the pressure drop. In this work, these interactions are analysed using two case studies. The results indicate that, from the thermal point of view, the incorporation of new heat exchangers is recommended in series. The limit is the point where the increase of the total pressure drop causes a reduction in the overall volumetric flow rate. New coolers added in parallel create a reduction of pressure drop and an increase in the overall water flow rate; however, this increase is not enough to counteract the reduction of fluid velocity and heat capacity removal.


Author(s):  
Sun-Joon Byun ◽  
Sang-Jae Lee ◽  
Jae-Min Cha ◽  
Zhen-Huan Wang ◽  
Young-Chul Kwon

This study presents the comparison of heat transfer capacity and pressure drop characteristics between a basic fin-tube heat exchanger and a modified heat exchanger with the structural change of branch tubes and coiled turbulators. All experiments were carried out using an air-enthalpy type calorimeter based on the method described in ASHRAE standards, under heat exchanger experimental conditions. 14 different kinds of heat exchangers were used for the experiment. Cooling and heating capacities of the turbulator heat exchanger were excellent, compared to the basic one. As the insertion ratio of the coiled turbulator and the number of row increased, the heat transfer performance increased. However, the capacity per unit area was more effective in 4 rows than 6 rows, and the cooling performance of the 6 row turbulator heat exchanger (100% turbulator insert ratio) was down to about 6% than that of 4 row one. As the water flow rate and the turbulator insertion ratio increased, the pressure drop of the water side increased. This trend was more pronounced in 6 rows. In the cooling condition, the pressure drop on the air side was slightly increased due to the generation of condensed water, but was insignificant under the heating condition. The power consumption of the pump was more affected by the water flow rate than the coiled turbulator. The equivalent hydraulic diameter of a tube by the turbulator was reduced and then the heat transfer performance was improved. Thus, the tube diameter was smaller, the heat flux was better.


Author(s):  
Shailesh N. Joshi ◽  
Danny J. Lohan ◽  
Ercan M. Dede

Abstract The heat transfer and fluid flow performance of a hybrid jet plus multipass microchannel heat sink in two-phase operation is evaluated for the cooling of a single large area, 3.61 cm2, heat source. The two-layer branching microchannel heat sink is evaluated using HFE-7100 as the coolant at three inlet volumetric flow rates of 150, 300, and 450 ml/min. The boiling performance is highest for the flow rate of 450 ml/min with the maximum heat flux value of 174 W/cm2. Critical heat flux (CHF) was observed at two of the tested flow rates, 150 and 300 ml/min, before reaching the maximum operating temperature for the serpentine heater. At 450 ml/min, the heater reached the maximum allowable temperature prior to observing CHF. The maximum pressure drop for the heat sink is 34.1 kPa at a heat flux of 164 W/cm2. Further, the peak heat transfer coefficient value of the heat sink is 28,700 W/m2 K at a heat flux value of 174 W/cm2 and a flow rate of 450 ml/min. Finally, a validated correlation of the single device cooler is presented that predicts heat transfer performance and can be utilized in the design of multidevice coolers.


Author(s):  
Ravi Arora ◽  
Anna Lee Tonkovich ◽  
Mike J. Lamont ◽  
Thomas Yuschak ◽  
Laura Silva

The two important considerations in the design of a heat exchanger are — the total heat transfer rate and the allowable pressure drop. The allowable pressure drop defines the maximum flow rate through a single microchannel and economics drives the design towards this flow rate. Typically the flow rate in the microchannel is in laminar flow regime (Re < 2000) due to smaller hydraulic diameter. The laminar flow heat transfer in a smooth microchannel is limited by the boundary layer thickness. Commonly the heat transfer rate is enhanced by passively disrupting the laminar boundary layer using protrusions or depressions in the channel walls. More often these methods are best applicable at small range of Reynolds number where the heat transfer rate enhancement is more than the pressure drop increase and break down as the flow rate is changed outside the range. The benefit of a flow disruption method can be reaped only if it provides higher heat transfer enhancement than the increase in the pressure drop at the working flow rates in the microchannel. A heat transfer efficient microchannel design has been developed using wall features that create stable disrupted flow and break the laminar boundary layer in a microchannel over a wide range of flow rates. The paper experimentally investigates the developed design for the heat transfer enhancement and pressure drop increase compared to a smooth wall microchannel. A simple microchannel device was designed and fabricated with and without wall features. The experiments with single gas phase fluid showed promising results with the developed wall feature design as the heat transfer rate increase was 20% to 80% more than the pressure drop increase in the laminar regime. The wall feature design was an important variable to affect the magnitude of performance enhancement in different flow regime. A general criterion was developed to judge the efficacy of wall feature design that can be used during a microchannel heat exchanger design.


Author(s):  
Zahir Uddin Ahmed ◽  
Md. Roni Raihan ◽  
Omidreza Ghaffari ◽  
Muhammad Ikhlaq

Abstract Microchannel heat sink is an effective method in compact and faster heat transfer applications. This paper numerically investigates thermal and hydraulic characteristics of a porous microchannel heat sink (PMHS) using various nanofluids. The effect of porosity, inlet velocity and nanoparticle concentration on thermal-hydraulic performance is systematically examined. The result shows a significant temperature increase (40°C) of the coolant in the porous zone. The pressure drop reduces by 35% for γ = 0.32 compared to the non-porous counterpart, and this reduction of pressure significantly continues when γ further increases. The pressure drop with win is linear for PMHS with nanofluids, and the change in pressure drop is steeper for nanofluids compared to their base fluids. The average heat transfer coefficients increases about 2.5 times for PMHS, and a further increase of 6% in is predicted with the addition of nanoparticle. The average Nusselt number increases non-linearly with Re for PMHS. The friction factor reduces by 50% when γ increases from 0.32 to 0.60, and the effect of nanofluid on friction factor is insignificant beyond the mass flow rate of 0.0004 kg/s. Whilst Cu and CuO nanoparticles help to dissipate the larger amount of heat from the microchannel, Al2O3 nanoparticle appears to have a detrimental effect on heat transfer. The thermal-hydraulic performance factor strongly depends on the nanoparticles, and it slightly decreases with the mass flow rate. The increase of nanoparticle concentration, in general, enhances both h and ΔP linearly for the range considered.


2013 ◽  
Vol 709 ◽  
pp. 286-291 ◽  
Author(s):  
Li Feng Wang ◽  
Bao Dong Shao ◽  
He Ming Cheng

The purpose of this paper is to optimize the structural sizes of multi-layer rectangle micro-channel heat sink, which has been widely used to cool electronic chip for its high heat transfer coefficient and compact structure. Taking the thermal resistance and the pressure drop as goal functions, a binary-objective optimization model was proposed for the multi-layer rectangle micro-channel heat sink based on Sequential Quadratic Programming (SQP) method. The number of optimized micro-channel in width n1 and that in height n2 are 21 and 7, the width of optimized micro-channel Wc and fin Wf are 340 and 130μm, the height of optimized micro-channel Hc is 415μm, and the corresponding total thermal resistance of the whole micro-channel heat sink is 1.3354 °C/W. The corresponding pressure drop is about 1.3377 Pa. When the velocity of liquid is larger than 0.3 m/s, the effect of change of velocity of liquid on the thermal resistance and pressure drop can be neglected.


Author(s):  
Noris Gallandat ◽  
Danielle Hesse ◽  
J. Rhett Mayor

The purpose of this paper is to demonstrate the possibility to selectively tune the convective heat transfer coefficient in different sections of a heat sink by varying the density of micro-features in order to minimize temperature gradients between discrete heat sources positioned along the flow path. Lifetime of power electronics is strongly correlated to the thermal management of the junction. Therefore, it is of interest to have constant junction temperatures across all devices in the array. Implementation of micro-feature enhancement on the convective side improves heat transfer due to an increase in surface area. Specific shapes such as micro hydrofoils offer a reduced pressure drop allowing for combined improvement of heat transfer and flow performance. This study presents experimental results from an array of three discrete heat source (20 × 15 mm) generating 100 W/cm2 and positioned in line along the flow path with a spacing of 10 mm between each of the sources. The heat sink was machined out of aluminum 6061 and micro-hydrofoils with a characteristic length of 500 μm were embedded in the cold plate. The cooling medium used is water at a flow rate of 3.6–13.4 g/s corresponding to a Reynolds number of 420–1575. It is demonstrated that the baseplate temperature can be maintained below 90°C and the difference between the maximum temperatures of each heat source is less than 6.7 °C at a heat flux of 100 W/cm2 and a water flow rate of 4.8 g/s.