Expert system for the on-line diagnosis of anaerobic wastewater treatment plants

2002 ◽  
Vol 45 (10) ◽  
pp. 195-200 ◽  
Author(s):  
A. Puñal ◽  
J. Rodríguez ◽  
E.F. Carrasco ◽  
E. Roca ◽  
J.M. Lema

A diagnosis system for anaerobic wastewater treatment processes is presented. The system is able to recognise the state and trend of the operation and suggest the appropriate control action. The on-line variables measured were gas flow rate and composition (methane and carbon monoxide), feed and recycling flow rates, temperature and pH, while the manipulable inputs are feed, recycling and buffer-addition flow rates. The diagnosis system comprises a structured rule base, incorporating expert knowledge using fuzzy logic features. The structure of the system is based on the classification of information related to the process in three categories: i) the state of the process, ii) its trend and iii) the recommended set-point values for the inputs manipulated: feeding, buffer and recycling pumps. The system was applied to diagnose the operation of a 1.1 m3 hybrid UASB-UAF treating wastewater from a fibreboard production factory under different conditions (overload and underload), corresponding to some of the typical causes of destabilisation in anaerobic wastewater treatment plants. These situations require control action in order to maintain the stability and the treatment capacity of the reactor. The application of the system developed for the purpose of managing the situation proved to be reliable for supplying the actual state and trend of the process, as well as the adequate set point values to recover stable operation and/or to avoid further destabilisation.

1987 ◽  
Vol 19 (3-4) ◽  
pp. 669-680 ◽  
Author(s):  
Gordon W. Speirs ◽  
Robert D. Hill

As part of a full-scale project to demonstrate the advantages of using automated process control in wastewater treatment plants, on-line sensors used in various control loops were calibrated and/or verified during control system commissioning and startup. The on-line measurements included liquid flow rates, air flow rates, suspended solids concentrations, and dissolved oxygen concentrations. The methods used to confirm instrument performance are presented along with results that show that several instruments were found to operate outside the manufacturers' written specifications. In addition, on-line methods which can help determine when recalibrations are required, and thereby help to reduce maintenance costs and ensure reliability, are also presented.


1996 ◽  
Vol 33 (1) ◽  
pp. 81-87
Author(s):  
L. Van Vooren ◽  
P. Willems ◽  
J. P. Ottoy ◽  
G. C. Vansteenkiste ◽  
W. Verstraete

The use of an automatic on-line titration unit for monitoring the effluent quality of wastewater plants is presented. Buffer capacity curves of different effluent types were studied and validation results are presented for both domestic and industrial full-scale wastewater treatment plants. Ammonium and ortho-phosphate monitoring of the effluent were established by using a simple titration device, connected to a data-interpretation unit. The use of this sensor as the activator of an effluent quality proportional sampler is discussed.


1999 ◽  
Vol 39 (4) ◽  
pp. 103-111 ◽  
Author(s):  
Frank Obenaus ◽  
Karl-Heinz Rosenwinkel ◽  
Jens Alex ◽  
Ralf Tschepetzki ◽  
Ulrich Jumar

This report presents the main components of a system for the model-based control of aerobic biological wastewater treatment plants. The crucial component is a model which is linked to the actual processes via several interfaces and which contains a unit which can immediately follow up the current process state. The simulation calculation of the model is based on data which are yielded by on-line measuring devices. If the sensors should fail at times, there are available a number of alternative concepts, some of which are based on the calculations of artificial neural networks or linear methods.


1997 ◽  
Vol 36 (1) ◽  
pp. 129-137 ◽  
Author(s):  
Vibeke R. Borregaard

In the upgrade of wastewater treatment plants to include biological nutrient removal the space available is often a limiting facor. It may be difficult to use conventional suspended growth processes (i.e. activated sludge) owing to the relatively large surface area required for these processes. Recent years have therefore seen a revived interest in treatment technologies using various types of attached growth processes. The “new” attached growth processes, like the Biostyr process, utilise various kinds of manufactured media, e.g. polystyrene granules, which offer a high specific surface area, and are therefore very compact. The Biostyr plants allow a combination of nitrification-denitrification and filtration in one and the same unit. The results obtained are 8 mg total N/l and an SS content normally below 10 mg/l. The plants in Denmark which have been extended with a Biostyr unit have various levels of PLC control and on-line instrumentation.


2019 ◽  
Vol 290 ◽  
pp. 121814 ◽  
Author(s):  
Giorgio Mannina ◽  
Taise Ferreira Rebouças ◽  
Alida Cosenza ◽  
Miquel Sànchez-Marrè ◽  
Karina Gibert

Sign in / Sign up

Export Citation Format

Share Document