scholarly journals Development of a Multi-Well Pairing System for Groundwater Heat Pump Systems

Energies ◽  
2018 ◽  
Vol 11 (12) ◽  
pp. 3485 ◽  
Author(s):  
Hongkyo Kim ◽  
Yujin Nam ◽  
Sang mu Bae ◽  
Oun Jeoun

Groundwater heat pump systems (GWHPs) can achieve higher coefficient of performance (COP) than air-source heat pump systems by using the relatively stable temperature of groundwater. Among GWHPs, multi-well systems have lower initial investment costs than conventional closed-loop geothermal systems, because they typically require installation of fewer boreholes for the same building load. However, the performance of GWHPs depends significantly on the groundwater properties, such as groundwater temperature, permeability and water quality. Moreover, pumping and injecting of groundwater during long-term operation may lead to problems such as overflow or clogging of the wells. In order to ensure reliable energy from ground sources, the development of sustainable operation methods for multi-well systems is essential for preventing overflow and well clogging. In this study, we have developed a pairing technology that connects the injection and supply wells through a spillway. This pairing technology can be used to control groundwater levels in wells and can be sustainably operated. To accurately estimate the performance of a multi-well system with the proposed pairing technology, the heating and cooling performance of the developed system was compared to that of a standing column well (SCW) system in a field-scale experiment. Furthermore, the effects of the multi-well pairing system on groundwater levels in the injection well were analyzed by numerical simulation. Moreover, in order to decide the required conditions of the multi-well pairing system, case studies were conducted under various hydraulic conductivity and pumping conditions.

2020 ◽  
Author(s):  
Alejandro García-Gil ◽  
Miguel Ángel Marazuela ◽  
Miguel Mejías Moreno ◽  
Enric Vázquez-Suñè ◽  
Eduardo Garrido Schneider ◽  
...  

<p>Shallow geothermal systems are the most efficient and clean technology for the air-conditioning of buildings and constitutes an emergent renewable energy resource in the worldwide market. Undisturbed systems are capable of efficiently exchanging heat with the subsurface and transferring it to human infrastructures, providing the basis for the successful decarbonisation of heating and cooling demands of cities. Unmanaged intensive use of groundwater for thermal purposes as a shallow geothermal energy (SGE) resource in urban environments threatens the resources´ renewability and the systems´ performance, due to the thermal interferences created by a biased energy demand throughout the year. To ensure sustainability, scientifically-based criteria are required to prevent potential thermal interferences between geothermal systems. In this work, a management indicator (balanced sustainability index, BSI) applicable to groundwater heat pump systems is defined to assign a quantitative value of sustainability to each system, based on their intrinsic potential to produce thermal interference. The BSI indicator relies on the net heat balance transferred to the terrain throughout the year and the maximum seasonal thermal load associated. To define this indicator, 75 heating-cooling scenarios based in 23 real systems were established to cover all possible different operational conditions. The scenarios were simulated in a standard numerical model, adopted as a reference framework, and thermal impacts were evaluated. Two polynomial regression models were used for the interpolation of thermal impacts, thus allowing the direct calculation of the sustainability indicator developed as a function of heating-cooling ratios and maximum seasonal thermal loads. The BSI indicator could provide authorities and technicians with scientifically-based criteria to establish geothermal monitoring programs, which are critical to maintain the implementation rates and renewability of these systems in the cities.</p>


1989 ◽  
Vol 111 (4) ◽  
pp. 353-357 ◽  
Author(s):  
V. C. Mei ◽  
F. C. Chen ◽  
B. Mathiprakasam

The performance of a groundwater thermoelectric (TE) heat pump system, based on today’s state-of-the-art TE materials, was calculated and compared with that of a conventional groundwater heat pump under the same water inlet temperature and flow rate. It was found that the TE system was competitive for cooling, particularly for groundwater temperatures below 18° C (64° F). The TE system performed poorly for heating mode operation. A cooling coefficient of performance (COP) of 6.4 could be realized by a properly designed TE system at a groundwater temperature of 13° C (55° F), compared with a COP of 4.35 for a conventional heat pump. For heating mode operation at the same water temperature, the TE system achieved a COP of 1.72, while the conventional heat pump performed at a COP of 3.72. Use of TE systems should be considered in areas where year-round cooling load dominates.


Water ◽  
2020 ◽  
Vol 12 (5) ◽  
pp. 1377 ◽  
Author(s):  
Hanna Choi ◽  
Jaeyeon Kim ◽  
Byoung Ohan Shim ◽  
Dong-hun Kim

The use of shallow geothermal energy systems utilizing groundwater temperature for the air-conditioning of buildings is increasing worldwide. The impact of these systems on groundwater quality has become crucial for environmental regulations and system design. For the long-term operation of geothermal systems, it is important to evaluate their influence on the geochemical properties of groundwater, including precipitation and dissolution of secondary minerals. This research was conducted in a real-scale geothermal system, consisting of a groundwater heat pump (GWHP). Hydrochemical data were obtained from samples collected from an aquifer before heating, during heating, and before cooling operations of the GWHP. The Langelier Saturation Index and Ryznar Stability Index were calculated, and the saturation index was simulated with the PHREEQC program. Evidence from water table variation, temperature change, and 87 Sr/ 86 Sr isotope distribution showed that groundwater flows from a well located on the northwest side of the geothermal well. The saturation index values showed that the pristine groundwater favors carbonate dissolution, however, manganese oxides are more sensitive to temperature than carbonate minerals. In addition, mineral precipitation and dissolution were found to vary with depth and temperature.


Author(s):  
Giulio Vialetto ◽  
Marco Noro ◽  
Masoud Rokni

In this paper, a new heat recovery for a microcogeneration system based on solid oxide fuel cell and air source heat pump (HP) is presented with the main goal of improving efficiency on energy conversion for a residential building. The novelty of the research work is that exhaust gases after the fuel cell are first used to heat water for heating/domestic water and then mixed with the external air to feed the evaporator of the HP with the aim of increasing energy efficiency of the latter. This system configuration decreases the possibility of freezing of the evaporator as well, which is one of the drawbacks for air source HP in Nordic climates. A parametric analysis of the system is developed by performing simulations varying the external air temperature, air humidity, and fuel cell nominal power. Coefficient of performance (COP) can increase more than 100% when fuel cell electric power is close to its nominal (50 kW), and/or inlet air has a high relative humidity (RH) (close to 100%). Instead, the effect of mixing the exhausted gases with air may be negative (up to −25%) when fuel cell electric power is 20 kW and inlet air has 25% RH. Thermodynamic analysis is carried out to prove energy advantage of such a solution with respect to a traditional one, resulting to be between 39% and 44% in terms of primary energy. The results show that the performance of the air source HP increases considerably during cold season for climates with high RH and for users with high electric power demand.


Author(s):  
Mohammad Omar Temori ◽  
František Vranay

In this work, a mini review of heat pumps is presented. The work is intended to introduce a technology that can be used to income energy from the natural environment and thus reduce electricity consumption for heating and cooling. A heat pump is a mechanical device that transfers heat from one environmental compartment to another, typically against a temperature gradient (i.e. from cool to hot). In order to do this, an energy input is required: this may be mechanical, electrical or thermal energy. In most modern heat pumps, electrical energy powers a compressor, which drives a compression - expansion cycle of refrigerant fluid between two heat exchanges: a cold evaporator and a warm condenser. The efficiency or coefficient of performance (COP), of a heat pump is defined as the thermal output divided by the primary energy (electricity) input. The COP decreases as the temperature difference between the cool heat source and the warm heat sink increases. An efficient ground source heat pump (GSHP) may achieve a COP of around 4. Heat pumps are ideal for exploiting low-temperature environmental heat sources: the air, surface waters or the ground. They can deliver significant environmental (CO2) and cost savings.


2021 ◽  
Author(s):  
Taha Sezer ◽  
Abubakar Kawuwa Sani ◽  
Rao Martand Singh ◽  
David P. Boon

<p>Groundwater heat pumps (GWHP) are an environmentally friendly and highly efficient low carbon heating technology that can benefit from low-temperature groundwater sources lying in the shallow depths to provide heating and cooling to buildings. However, the utilisation of groundwater for heating and cooling, especially in large scale (district level), can create a thermal plume around injection wells. If a plume reaches the production well this may result in a decrease in the system performance or even failure in the long-term operation. This research aims to investigate the impact of GWHP usage in district-level heating by using a numerical approach and considering a GWHP system being constructed in Colchester, UK as a case study, which will be the largest GWHP system in the UK. Transient 3D simulations have been performed pre-construction to investigate the long-term effect of injecting water at 5°C, into a chalk bedrock aquifer. Modelling suggests a thermal plume develops but does not reach the production wells after 10 years of operation. The model result can be attributed to the low hydraulic gradient, assumed lack of interconnecting fractures, and large (>500m) spacing between the production and injection wells. Model validation may be possible after a period operational monitoring.</p>


2011 ◽  
Vol 374-377 ◽  
pp. 398-404 ◽  
Author(s):  
Ying Ning Hu ◽  
Ban Jun Peng ◽  
Shan Shan Hu ◽  
Jun Lin

A hot-water and air-conditioning (HWAC) combined ground sourse heat pump(GSHP) system with horizontal ground heat exchanger self-designed and actualized was presented in this paper. The heat transfer performance for the heat exchanger of two different pipe arrangements, three layers and four layers, respectively, was compared. It showed that the heat exchange quantity per pipe length for the pipe arrangement of three layers and four layers are 18.0 W/m and 15.0 W/m. The coefficient of performance (COP) of unit and system could remain 4.8 and 4.2 as GSHP system for heating water, and the COP of heating and cooling combination are up to 8.5 and 7.5, respectively. The power consumption of hot-water in a whole year is 9.0 kwh/t. The economy and feasibility analysis on vertical and horizontal ground heat exchanger were made, which showed that the investment cost per heat exchange quantity of horizontal ground heat exchanger is 51.4% lower than that of the vertical ground heat exchanger, but the occupied area of the former is 7 times larger than the latter's.


Energies ◽  
2018 ◽  
Vol 11 (10) ◽  
pp. 2642 ◽  
Author(s):  
Yi Zhang ◽  
Guanmin Zhang ◽  
Aiqun Zhang ◽  
Yinhan Jin ◽  
Ruirui Ru ◽  
...  

Frost layer on the outdoor air heat exchanger surface in an air-source heat pump (ASHP) can decrease the system coefficient of performance (COP). Although the common defrosting and anti-frosting methods can improve the COP, the periodic defrosting not only reduces the system energy efficiency but also deteriorates the indoor environment. To solve these problems, it is necessary to clearly understand the frosting phenomenon and to achieve the system frost-free operation. This paper focused firstly on the analyses of frosting pathways and frosting maps. Followed by summarizing the characteristics of frost-free technologies. And then the performances of two types of frost-free ASHP (FFASHP) systems were reviewed, and the exergy and economic analysis of a FFASHP heating system were carried out. Finally, the existing problems related to the FFASHP technologies were proposed. Results show that the existing frosting maps need to be further improved. The FFASHP systems can not only achieve continuous frost-free operation but reduce operating cost. And the total COP of the FFASHP heating system is approximately 30–64% higher than that of the conventional ASHP system under the same frosting conditions. However, the investment cost of the FFASHP system increases, and its reliability also needs further field test in a wider frosting environment. In the future, combined with a new frosting map, the control strategy for the FFASHP system should be optimized.


Author(s):  
Wu Huagen ◽  
Shu Pengcheng ◽  
Zhao Yuanyang ◽  
Xing Ziwen

The air-source heat pump has been widely used in industrial refrigeration and central air-conditioning applications because of its unique superiority. An important consideration in the design of heat pump is improving its COP (coefficient of performance). In this paper, the results of experimental investigation on the effects of alternative refrigerants (R22, R134a, R404A and R407C) and economizer on the performance of heat pump are presented. The COP of the heat pump used R134a is up to 4.5% higher than R22, but its capacity got a 37.08% decrease. The refrigerant R407C applied in heat pump can improve the capacity up to 7.86% than R22, but its COP shows a decrease up to 5.92%. The refrigerant R404A used in heat pump will result in poor capacity and COP compared to R22. The economizer system used in heat pump will improve the COP, but as the superfeed pressure of the economizer increases, the system COP increases first, and then drops. So there exists an optimal superfeed pressure of the economizer for the best COP. Also, the effect of the economizer on the screw compressor performance is analyzed by recording the P-v indicator diagram.