scholarly journals The influence of the network asymmetry on the settings and sensitivity of an earth fault protection using higher harmonics

2019 ◽  
Vol 84 ◽  
pp. 02008
Author(s):  
Lubomir Marciniak ◽  
Mateusz Piątek

Detection of high resistance earth faults in medium voltage networks is an important problem due to ineffectiveness of traditional earth fault protections. Such short circuits can be detected by the criterion of a reactive power of higher harmonics for zero sequence current and voltage. The main problem is determination of the power setting value in the protection, which depends on the asymmetry of phase-to-earth capacitances and higher harmonics in supply voltages, which are generated by non-linear loads. The intensive tests of the asymmetry of the zero sequence currents and voltages for harmonics and their reactive power have been carried out in 15 kV compensated network as a function of all relevant parameters, i.e.: maximum capacitance deviation of the network and protected line, percentage content of harmonics in supply voltages, capacitive current of the network and the line. It has been shown that third harmonics of the zero sequence voltage and current are the best suited for practical use, since the asymmetry reactive power of these components is the smallest among the considered harmonics and the protection sensitivity will be the highest.

Vestnik IGEU ◽  
2019 ◽  
pp. 30-41
Author(s):  
Yu.D. Kutumov ◽  
V.V. Tyutikov ◽  
T.Yu. Shadrikova ◽  
V.A. Shuin

In distribution 6–10 kV networks with an insulated neutral for earth fault protection, zero sequence current directional protection devices are commonly used. According to the operation data, the main disadvantage of such kind of protection is the possibility of their functioning failures in transient conditions with the most dangerous for network intermittent arc earth faults. It is known that most earth faults in 6–10 kV networks, primarily in the initial stage of insulation damage, have an intermittent arc. Operation failures of zero sequence current directional protection in case of arc faults reduce the operational reliability of the protected network and, as a result, the reliability of power supply to consumers. Nowadays, new developments of electrical power systems relay protection devices, including earth fault protection of medium voltage distribution electrical networks, are implemented only on a microprocessor base. Therefore, the selection and justification of the implementation principles of zero sequence current directional protection which can provide high dynamic stability of functioning is a relevant objective. When analyzing the dynamic stability of the functioning of zero sequence directional current protection, regarding the complexity of transients during intermittent arc earth faults in medium voltage electrical networks with an isolated neutral, the simulation in Matlab using SimPowerSystem and Simulink was carried out. This study focuses on transient currents and voltages as the main factor influencing dynamic stability of the functioning of zero sequence current directional protection. The impact of other factors, for example, the inaccuracies of the primary zero sequence current and voltage transducers, the scheme of formation of compared quantities, etc. was not taken into account in simulation models. The study has allowed determining the causes of possible functioning failures of digital current earth fault directional protection in dynamic operation modes. It has been shown that the usage of orthogonal components of fundamental frequency of zero sequence voltage and current in current directional protection devices eliminates the failure of their operation with any kind of arc earth faults. To ensure high dynamic stability of operation under the influence of transients during arc intermittent earth faults, current directional protection for this type of damage should be performed on the basis of monitoring the phase relationships of the fundamental frequency components of 50 Hz of zero sequence voltage and current, but not their full values.


Energies ◽  
2020 ◽  
Vol 13 (5) ◽  
pp. 1293 ◽  
Author(s):  
Krzysztof Lowczowski ◽  
Jozef Lorenc ◽  
Jozef Zawodniak ◽  
Grzegorz Dombek

The paper analyzes the utilization of cable screen currents for earth fault identification and location. Attention is paid on cable and mixed feeders—cable and overhead lines. The principle of operation is based on utilization of 3 criterion values: Ratio of cable screen earthing current and zero sequence cable core current—RF110/15, phase shift between cable screen earthing current and zero sequence cable core current—α and cable screen admittance defined as a ratio of cable screen earthing current and zero sequence voltage—Y0cs. Earth fault location is possible thanks to discovered relation between RF110/15 and α, whereas Y0cs allows for reliable detection of earth faults. Detection and identification are very important because it allows to increase the reliability of supply—reduce downtime and number of consumers affected by the fault. The article presents a phase to ground fault current flow for different power system configurations. At the end solution, which improves location capabilities is proposed. The solution is analyzed in PSCAD software and verified by network experiment.


2006 ◽  
Vol 19 (3) ◽  
pp. 429-438 ◽  
Author(s):  
Dumitru Toader ◽  
Stefan Haragus ◽  
Constantin Blaj

A major problem concerning the operation of medium voltage power networks refers to the neutral-point grounding system. Several technical solutions are in use, none of them being completely satisfactory. One criterion to appreciate the efficiency of a grounding system is the ability of the network?s protective system to accurately detect various types of faults such as broken conductor with ground contact faults. This type of fault make a relatively important figure (3 to 10 %) in the total faults statistics for a medium voltage network. In order to detect such faults, the sensed variables are the zero-sequence voltage and the neutral-grounding current. In this paper an analytical and computational analysis is performed to see how various fault and network parameters affect these variables, assuming different grounding systems. Measurements made in two real medium voltage networks show good agreement with the theoretical results.


Energies ◽  
2019 ◽  
Vol 12 (12) ◽  
pp. 2361
Author(s):  
Muxuan Xiao ◽  
Feng Wang ◽  
Zhixing He ◽  
Honglin Ouyang ◽  
Renyifan Hao ◽  
...  

The cascaded H-bridge static var generator (SVG) has been employed to provide reactive power and regulate grid voltages for many years because of its good modularity, easy scalability, and improved harmonic performance. A novel cluster-balancing power control method combining negative-sequence currents and zero-sequence voltage is proposed to redistribute the unbalanced active powers and eliminate the power oscillation under asymmetrical conditions. Simultaneously, the dynamic performance of the SVG power balance control can be improved under asymmetrical conditions with the zero-sequence voltage expression derived in this paper. On the basis of the proposed method, the fault ride through capability of star-connected SVG under asymmetrical conditions is compared among active power oscillation elimination (APOE), reactive power oscillation elimination (RPOE), and balanced positive sequence current (BPSC) injection references calculation strategies from the perspective of the zero-sequence voltage, maximum phase voltage, and maximum phase current. The method provides the theoretical reference for power control under asymmetric conditions and the analysis results show that under asymmetrical conditions, the current of BPSC is minimal and symmetrical, while the RPOE has the least voltage and no zero- sequence voltage needs to be injected. Finally, the results of simulation and experiment have been given to verify the theoretical studies.


Energies ◽  
2020 ◽  
Vol 13 (22) ◽  
pp. 6017
Author(s):  
Tomasz Popławski ◽  
Marek Kurkowski ◽  
Jarosław Mirowski

The issues that are presented in the article concern the broadly understood parameters of the operation of lighting fixtures in mixed systems and the improvement of the quality of electricity, considered in two aspects: as receivers of the energy consumed, determining and generating reactive power, influencing the asymmetry of currents and the production of higher harmonics, determined by the parameters of current and supply voltage (independent of the consumers connected at the connection point), which are influenced by the consumers that are connected at the connection point. After the tests, in order to improve the quality of energy, a proprietary program for the design of passive resonance filters was developed. A wide range of measurements of various types of lighting devices was carried out in single, complex, and mixed systems. Luminaires with discharge and LED sources were selected for the analysis of energy parameters. The tests were carried out in accordance with the IEEE 1459-2010 standard for single-phase circuits with distorted waveforms.


Energies ◽  
2019 ◽  
Vol 12 (16) ◽  
pp. 3190 ◽  
Author(s):  
Krzysztof Lowczowski ◽  
Jozef Lorenc ◽  
Jerzy Andruszkiewicz ◽  
Zbigniew Nadolny ◽  
Jozef Zawodniak

This paper presents novel zero sequence current filter and earth fault protection relay, which utilize cable screens earthing current in protection algorithm. Different problems connected with state of the art of zero sequence current filters and protection relays are presented and compared with the proposed solution. The presented concept is verified in PowerFactory simulation software, experiment concerning modeling the earth fault current flow in medium voltage (MV) cable supplied from the low voltage (LV) network and measurements in the MV network in the Polish distribution system. The proposed solution is characterized by higher sensitivity and reduced number of erroneous trips. The presented solution is suitable for any MV cable lines. Biggest advantages are observed in power output lines from renewable energy sources, which are often operated under no-load conditions.