Mathematical Modeling of THD Mitigation Using HAPF for UPS System with Experimental Analysis via Hybrid Interface of Optical USB and Power Quality Meter
This paper discusses a novel analysis scheme based on the hybrid interface of Optical USB and Power Quality Meter for measuring Total Harmonic Distortion (THD) that exists in the Uninterruptable Power Supply (UPS) system and connected load. The designed hybrid interface experimentally analyzes the power quality and harmonics of the Uninterrupted Power Supply (UPS) system, and mitigation is proposed with the proposed Single-Phase Hybrid Active Power Filter (HAPF) based on instantaneous Power Theory (PQ) with hysteresis control technique and synchronous frame reference (DQ) with hysteresis control techniques at nonlinear load. This study authenticates and gives appropriate measurements in analyzing the harmonics and voltage distortion during conversion of power. The designed work offers the compensation and elimination of harmonic currents using PQ and DQ theory at different nonlinear loads. The proposed HAPF for the UPS system has demonstrated the significant reduction in THD using proposed Power Theory (PQ) with hysteresis control technique from 46.58% to 1.51% and by using DQ theory with hysteresis control technique has reduced THD from 46.58% to 1.38%. Finally, the results are compared between PQ and DQ. It is validated via results that DQ theory eliminated harmonics and also having less THD as compared to PQ-theory. Furthermore, one of the key aspects of the work is the analysis of power quality using Optical USB Interface (OC4USB) and FLUKE series power quality analyzer.