Analyses and Monitoring of Power Grid

Author(s):  
Rana A. Jabbar ◽  
Muhammad Junaid ◽  
M. A. Masood ◽  
A. Bashir ◽  
M. Mansoor

Power system analyses and monitoring of power system engineering are as essential as oxygen for human beings. This innovative approach deals with a 132 kV grid simulation in electrical transient analyzer program (ETAP). The existing power distribution system in Pakistan consists of approximately six thousand 11 kV feeders, which are mainly analyzed by software FDR-ANA (Feeder Analyses). This software does not have capability to provide comprehensive analyses for integrated power system. The case under study is 132 kV grid situated in Gujranwala electric power company (GEPCO), one of the distribution companies (DISCO’s) of Pakistan electric power company (PEPCO) which has been selected for comprehensive analyses using ETAP software. This software performs numerical calculations of large integrated power system with fabulous speed, besides generating output reports. In a developing country like Pakistan it is first time that analyses based Off-line monitoring has been made, which includes load flow, harmonic, transient, short circuit and ground grid analyses. In load flow analysis, current flowing in every branch, power factor, active and reactive power flow, line losses, voltage magnitude with angle etc. have been calculated. During harmonic analysis, distorted current and voltage waveforms along with their harmonic spectrum caused by non-linear loads have been recorded. Transient analysis has been performed to record different waveforms like variation in bus frequency, bus real power loading, bus voltage angle, and bus reactive power loading for short interval of time during transient conditions. In ground grid modeling, step, and touch potentials have been calculated in comparison with set standards. While performing short circuit analysis, all the possible short circuit faults like line to ground, double line to ground, 3-phase faults etc. on ½ cycle, 1.5 to 4 cycle, and 30 cycle networks have been performed to record the short circuit currents. These analyses have been executed using ETAP software, based upon historical data obtained from original system that will be very helpful for system security and reliability.

Author(s):  
Ahmad Fateh Mohamad Nor ◽  
Marizan Sulaiman ◽  
Aida Fazliana Abdul Kadir ◽  
Rosli Omar

Voltage instability analysis in electric power system is one of the most important factors in order to maintain the equilibrium of the power system. A power system is said to be unstable if the system is not able to maintain the voltage at all buses in the system remain unchanged after the system is being subjected to a disturbance.The research work presented in this paper is about the analysis of voltage instability of electric power system by using voltage stability margin (VSM), load real power (P) margin, reactive power (Q) margin, reactive power-voltage (QV) and real power-voltage (PV) modal analysis. IEEE 30-bus system has been chosen as the power system. The load flow analysis are simulated by using Power World Simulator software version 16. Both QV and PV modal analysis were done by using MATLAB application software.


2021 ◽  
Vol 23 (2) ◽  
pp. 157-163
Author(s):  
Awatif Nadia ◽  
Md. Sanwar Hossain ◽  
Md. Mehedi Hasan ◽  
Khondoker Ziaul Islam ◽  
Shahajan Miah

In the integrated power system network uncertainty can occur at any time. The transmission reliability (TRM) margin is the amount of transmission capacity that guarantees that the transmission network is protected from instability in the operating state of the system. The calculation of the available transfer capacity (ATC) of the transmission reliability margin should be included in a deregulated power system to ensure that the transmission network is safe within a fair range of uncertainties that arise during the power transfer. However, the TRM is conserved as a reliability margin to reflect the unpredictability of the operation of the electric system. Besides, the system operator (SO) utilizes the TRM value during unreliability by adjusting the ATC value some amount up or down to account for errors in data and uncertainty in the model. This paper describes a technique for TRM estimation by modified DCQ load flow method considering VAR transfer distribution factor. The main focus of this study is to get a new approach to determine TRM by incorporating with ATCQ considered reactive power and sensitivity w.r.t ATC considered voltage magnitude. This technique is applied to the IEEE 6 bus system, and results are compared with previous results for validation. The technique leads to more exact and secure estimates of transmission reliability margin.


Author(s):  
Ajith M ◽  
Dr. R. Rajeswari

Power-flow studies are of great significance in planning and designing the future expansion of power systems as well as in determining the best operation of existing systems. Technologies such as renewables and power electronics are aiding in power conversion and control, thus making the power system massive, complex, and dynamic. HVDC is being preferred due to limitations in HVAC such as reactive power loss, stability, current carrying capacity, operation and control. The HVDC system is being used for bulk power transmission over long distances with minimum losses using overhead transmission lines or submarine cable crossings. Recent years have witnessed an unprecedented growth in the number of the HVDC projects. Due to the vast size and inaccessibility of transmission systems, real time testing can prove to be difficult. Thus analyzing power system stability through computer modeling and simulation proves to be a viable solution in this case. The motivation of this project is to construct and analyze the load flow and short circuit behavior in an IEEE 14 bus power system with DC link using MATLAB software. This involves determining the parameters for converter transformer, rectifier, inverter and DC cable for modelling the DC link. The line chosen for incorporation of DC link is a weak bus. This project gives the results of load flow and along with comparison of reactive power flow, system losses, voltage in an AC and an AC-DC system.


Author(s):  
Fadhel Putra Winarta ◽  
Yoli Andi Rozzi

The study of electric power flow analysis (Load Flow) is intended to obtain information about the flow of power or voltage in an electric power system network. This information is needed to evaluate the performance of the power system. Electrical power flow problems include calculating the flow and system voltage at certain terminals or buses. The benefits of this power flow study are to find out the voltage at each node in the system, to find out whether all the equipment meets the specified limits to deliver the desired power, and to obtain the original conditions in the new system planning. This study is divided into two: the analysis of data when the conditions have not been added wind turbine and after the addition of 300 kW wind turbine with software power station ETAP software 12.6.0 and the Newton-Raphson method will be used in analyzing the power flow of the electric power system. Based on the results of the tests, it is found that the overall value of losses for power flow before the addition of DG is 0.031 MW and 0.037 Mvar, for the voltage drop with the lowest percentage, namely on bus 10 with a percentage of 96.45 for the 0.4 kV system and the 20 kV system on bus 19 with a percentage of 99.03, the largest% PF load was in lump 1 with 98.64 and the smallest% PF was in lump7 with a value of 84.92. The short circuit data value on the 20 kV bus system at Andalas University before the addition of DG with 3-phase disturbances averaged 13.354 A, 1-phase disturbances averaged 3.521 A, 2-phase disturbances averaged 11.719 A and 2 ground phases of 12.842 A Whereas for the value of power flow after the addition of DG in the form of the wind turbine of 300 kW the overall value of losses is 0.032 MW and 0.042 MvarAR, for the voltage drop with the percentage for voltage drop with the lowest percentage is bus 10 with a percentage of 96.63 for system 0, 4 kV and a 20 kV system on bus 14 with a percentage of 98.1, the largest% PF load is in lump 1 with 98.64 and the smallest% PF is in lump7 with a value of 84.92. The short circuit data value on the 20 kV bus system at Andalas University after the addition of DG with 3 phase disturbances has an average value of 13.354 A, 1 phase disturbance averages 3.523 A, 2 phase disturbances average 11.737 A and 2 phases ground is 12.059 A For the source in this system, after the addition of DG, there was a change in the% PF of the PLN grid, namely 79.53 and the wind turbine -83%.


2018 ◽  
Vol 3 (2) ◽  
Author(s):  
Sunday Adetona ◽  
Emenike Ugwuagbo ◽  
Frank Okafor ◽  
Tolulope Akinbulire

Injection of a new power system component into an existing power grid often cause change in the behaviour of the power grid to which it is injected. Therefore, forecasting possible unsafe condition(s) of the power grid using an efficient power study tool is essential; and, provision of necessary mitigation actions to ensure a reliable grid is important. This paper, therefore, presents evacuation study of a 400 MW power plant connecting to the 15 GW planned transmission network of the Transmission Company of Nigeria (TCN). The NEPLAN power system analytical software was used in the modelling and simulation of the electric power grid. In the research, load flow, short circuit, transient stability, and contingency analyses were performed on the case study. From the short circuit study, it is observed that if TCN network expansion program is fully implemented, the short circuit level will go beyond the existing switchgear ratings in major substations of the network. However, with the introduction of substation splitting at Omotoso and ongoing Ogijo substations, the short circuit level will be reduced by 15%; leading to improvement in the overall system stability. Keywords—Load flow, short circuit study, transient stability study, and contingency analysis


Author(s):  
Ahmed Zkear Abass

<p><span>Iraq is facing deficiency of electric power for last decades. The main reason for deficiency of electric power is due to less respect of analytical load flow studies of electric supply substation. To stop and overcome such situation in future, researchers should be analyzing different power substation focusing on load flow studies, short circuit studies and protection schemes. Due to lack of research and studies on load flow and fault analysis, Iraq is facing a lot of issues, such as power failures and high copper losses, solving of these problems on substation level, demand a high familiarity about the power system. In this paper we analyses combined typical gas station with solar thermal power station and survey load flow, short circuit, transient stability, and voltage drop before and after combined station by using electrical transient analyzer program (ETAP). Now a day’s power supply reliability and goodness are big interest. analyses of power system are a main part in power system designing and planning, in order to accommodate future loads and the expansion of cities.</span></p>


Author(s):  
Hayatul Harifin ◽  
Novalio Daratha ◽  
M. Khairul Amri Rosa

AbstractLoad flow analysis is a study to plan and determine the amount of power in an electric power system. During its development, industry requires a large amount of electric power and uses electrical equipment as a means of production. The benefits of an electric load flow analysis are to find out the amount of power in the electric power system whether it still meets predetermined limits, and to find out the amount of voltage at each point, and to obtain initial conditions for the new system planning. Load flow analysis begins calculating the active power and reactive power at each node (bus) installed, loading on the channel or conductor, the load flow calculation will be assisted using the Julia program. From the results of calculations using the Julia program, the voltage at each point with the smallest stress is obtained, namely the 10th point of 209.89 - j10.34V for phase A, -107.39 - j186.87V for phase B, -108.12 + j178,51V for phase CKey Words: Drop Voltage, Julia, Load Flow


Author(s):  
Robi Kurniawan ◽  
Ardiansyah Nasution ◽  
Arnawan Hasibuan ◽  
Muzamir Isa ◽  
Muskan Gard ◽  
...  

Distributed Generation (DG) is a small capacity generator located in the electricity distribution system and is usually placed on buses that are connected directly to the load. Placement of distributed generation is one of the technical efforts to reduce voltage drop and power losses in the system. In addition, load flow analysis is a study to plan and determine the amount of power in an electric power system. The results of power losses after adding distributed generation were the best in the fifth experiment on bus 149, where the system experienced a total loss of active power (P) previously of 720,822 kW, to 682,939 kW and total loss of reactive power (Q) previously of 530.02 kVar, to 405.835 kVar. From the results of the calculation of the power flow using ETAP software (Electrical Transient Analyzer Program). So, it can be concluded that the electrical network system can be said to be good. The results obtained are the more DG (wind turbine generator) that is input into the bus it will reduce the voltage drop that occurs. After simulating the overall voltage drop, it still meets the standards according to the results of the Text Report on ETAP.


Sign in / Sign up

Export Citation Format

Share Document