scholarly journals METHOD FOR INCREASING THE FIRE EXTINGUISHING EFFICIENCY OF MODULES AUTOMATIC FIRE WATER MIST SPRAY EXTINGUISHERS SYSTEMS AT THE OBJECTS OF THE OIL AND GAS FACILITIES

Author(s):  
I.A Pustovalov ◽  
◽  
A.V Ivanov ◽  
2021 ◽  
Vol 11 (7) ◽  
pp. 3247
Author(s):  
Dong Hwan Kim ◽  
Chi Young Lee ◽  
Chang Bo Oh

In this study, the effects of discharge area and atomizing gas type in a twin-fluid atomizer on heptane pool fire-extinguishing performance were investigated under the heat release rate conditions of 1.17 and 5.23 kW in an enclosed chamber. Large and small full cone twin-fluid atomizers were prepared. Nitrogen and air were used as atomizing gases. With respect to the droplet size of water mist, as the water and air flow rates decreased and increased, respectively, the Sauter mean diameter (SMD) of the water mist decreased. The SMD of large and small atomizers were in the range of approximately 12–60 and 12–49 μm, respectively. With respect to the discharge area effect, the small atomizer exhibited a shorter extinguishing time, lower peak surface temperature, and higher minimum oxygen concentration than the large atomizer. Furthermore, it was observed that the effect of the discharge area on fire-extinguishing performance is dominant under certain flow rate conditions. With respect to the atomizing gas type effect, nitrogen and air appeared to exhibit nearly similar extinguishing times, peak surface temperatures, and minimum oxygen concentrations under most flow rate conditions. Based on the present and previous studies, it was revealed that the effect of atomizing gas type on fire-extinguishing performance is dependent on the relative positions of the discharged flow and fire source.


2014 ◽  
Vol 915-916 ◽  
pp. 356-361
Author(s):  
Zheng Wen Xie

FDS simulation software was used to establish the full size lampblack physics model of single wind pipe, using the orthogonal design method design of analog calculation conditions, research in the nozzle pressure, the droplet radius, nozzle, flow quantity and injection angle parameters under different conditions of water mist fire extinguishing effect. Based on a full-scale combustion and water mist fire extinguishing experiment, the water mist fire suppression was observed and test analysis etc, to better understand the flue water mist fire extinguishing feasibility, provides the theory basis for the design of efficient, reliable flue fire extinguishing system.


2013 ◽  
Vol 790 ◽  
pp. 53-56
Author(s):  
Chen Jian ◽  
Xu Yan Ying ◽  
Wang Na

This paper presents an experimental study of fire suppression effectiveness with water mist containing FeCl2 additives.The investigation focuses on suppression effectiveness under various FeCl2 additives concentrations,working pressures and nozzle different height above the fire source . The experimental results show that: there is a significant impact on fire suppression effectiveness when adding FeCl2 to water mist. There is an optimum additive concentration of extinguishing fire, corresponding to the shortest extinguishing time, the least amount of water, the highest efficiency of extinguishing fire. The nozzle working pressures and nozzle position have effect on the performance of the water mist extinguishing: the greater the pressure is, the shorter water mist fire extinguishing time is. Under the same experimental conditions, the closer the water mist nozzles are to the oil pan, the shorter extinguishing time is.


Sign in / Sign up

Export Citation Format

Share Document