scholarly journals An Adaptive Protection Scheme for Coordination of Distance and Directional Overcurrent Relays in Distribution Systems Based on a Modified School-Based Optimizer

Electronics ◽  
2021 ◽  
Vol 10 (21) ◽  
pp. 2628
Author(s):  
Mohamed Abdelhamid ◽  
Salah Kamel ◽  
Ahmed Korashy ◽  
Marcos Tostado-Véliz ◽  
Fahd A Banakhr ◽  
...  

This paper presents an adaptive protection scheme (APS) for solving the coordination problem that deals with coordination directional overcurrent relays (DOCRs) and distance relays second zone time, in relation to coordination with DOCRs. The coordination problem becomes more complex with the impact of renewable energy sources (RES) when added to the distribution grid. This leads to a change in the grid topology, caused by the on/off states of the distribution generators (DG). The frequency of topological changes in distribution grids poses a challenge to the power system’s protection components. The change in the state of DGs leads to malfunction in reliability and miscoordination between protection relays, since that causes a direct effect to the short circuit currents. This paper used the school-based optimization (SBO) algorithm, which simulates the educational process, in order to deal with coordination problems. That algorithm is modified (MSBO) by modified both learning and teaching processes. The IEEE 8-bus test system and IEEE 14-bus distribution network are used to validate the proposed coordination system’s effectiveness when dealing with the coordination process between distance and DOCRs, at both the near- and far-end in the typical topological grid and with DGs in working order.

Processes ◽  
2021 ◽  
Vol 9 (3) ◽  
pp. 471
Author(s):  
Eman S. Ali ◽  
Ragab A. El-Sehiemy ◽  
Adel A. Abou El-Ela ◽  
Karar Mahmoud ◽  
Matti Lehtonen ◽  
...  

The output generations of renewable energy sources (RES) depend basically on climatic conditions, which are the main reason for their uncertain nature. As a result, the performance and security of distribution systems can be significantly worsened with high RES penetration. To address these issues, an analytical study was carried out by considering different penetration strategies for RES in the radial distribution system. Moreover, a bi-stage procedure was proposed for optimal planning of RES penetration. The first stage was concerned with calculating the optimal RES locations and sites. This stage aimed to minimize the voltage variations in the distribution system. In turn, the second stage was concerned with obtaining the optimal setting of the voltage control devices to improve the voltage profile. The multi-objective cat swarm optimization (MO-CSO) algorithm was proposed to solve the bi-stages optimization problems for enhancing the distribution system performance. Furthermore, the impact of the RES penetration level and their uncertainty on a distribution system voltage were studied. The proposed method was tested on the IEEE 34-bus unbalanced distribution test system, which was analyzed using backward/forward sweep power flow for unbalanced radial distribution systems. The proposed method provided satisfactory results for increasing the penetration level of RES in unbalanced distribution networks.


2017 ◽  
Vol 2017 ◽  
pp. 1-16 ◽  
Author(s):  
Beibei Wang ◽  
Xiaoqing Hu ◽  
Peifeng Shen ◽  
Wenlu Ji ◽  
Yang Cao ◽  
...  

There are many uncertain factors in the modern distribution network, including the access of renewable energy sources and the heavy load level. The existence of these factors has brought challenges to the stability of the power distribution network, as well as increasing the risk of exceeding transmission capacity of distribution lines. The appearance of flexible load control technology provides a new idea to solve the above problems. Air conditioners (ACs) account for a great proportion of all loads. In this paper, the model of dispatching AC loads in the regional power grid is constructed, and the direct load control (DLC) method is adopted to reduce the load of ACs. An improved tabu search technique is proposed to solve the problem of network dispatch in distribution systems in order to reduce the resistive line losses and to eliminate the transmission congestion in lines under normal operating conditions. The optimal node solution is obtained to find the best location and reduction capacity of ACs for load control. To demonstrate the validity and effectiveness of the proposed method, a test system is studied. The numerical results are also given in this article, which reveal that the proposed method is promising.


2021 ◽  
Vol 11 (2) ◽  
pp. 774 ◽  
Author(s):  
Ahmed S. Abbas ◽  
Ragab A. El-Sehiemy ◽  
Adel Abou El-Ela ◽  
Eman Salah Ali ◽  
Karar Mahmoud ◽  
...  

In recent years, with the widespread use of non-linear loads power electronic devices associated with the penetration of various renewable energy sources, the distribution system is highly affected by harmonic distortion caused by these sources. Moreover, the inverter-based distributed generation units (DGs) (e.g., photovoltaic (PV) and wind turbine) that are integrated into the distribution systems, are considered as significant harmonic sources of severe harmful effects on the system power quality. To solve these issues, this paper proposes a harmonic mitigation method for improving the power quality problems in distribution systems. Specifically, the proposed optimal planning of the single tuned harmonic filters (STFs) in the presence of inverter-based DGs is developed by the recent Water Cycle Algorithm (WCA). The objectives of this planning problem aim to minimize the total harmonic distortion (THD), power loss, filter investment cost, and improvement of voltage profile considering different constraints to meet the IEEE 519 standard. Further, the impact of the inverter-based DGs on the system harmonics is studied. Two cases are considered to find the effect of the DGs harmonic spectrum on the system distortion and filter planning. The proposed method is tested on the IEEE 69-bus distribution system. The effectiveness of the proposed planning model is demonstrated where significant reductions in the harmonic distortion are accomplished.


2012 ◽  
Vol 516-517 ◽  
pp. 1316-1321
Author(s):  
Ming Ta Yang ◽  
Jin Lung Guan ◽  
Jhy Cherng Gu

Wind generator and distribution systems after interconnection would change the short circuit fault characteristics of the original system and may lead to protection relay malfunctions, and review of the protection coordination. It is necessary to research the impact of existing protection strategies for distribution systems after wind generator interconnection. Linear programming methods were adopted for this study to review the coordination problems among feeder circuit breaker, lateral circuit breaker, and power fuse after radial distribution systems and wind generator interconnections.


2018 ◽  
Vol 7 (3) ◽  
pp. 223-231
Author(s):  
Saad Muftah Saad ◽  
Naser El Naily ◽  
Faisal A. Mohamed

The environmental and economic features of renewable energy sources have made it possible to be integrated as Distributed Generation (DG) units in distribution networks and to be widely utilized in modern distribution systems. The intermittent nature of renewable energy sources, altering operational conditions, and the complex topology of active distribution networks makes the level of fault currents significantly variable. Thus, the use of distance protection scheme instead of conventional overcurrent schemes offers an appropriate alternative for protection of modern distribution networks. In this study, the effect of integrating multiple DG units on the effective cover of distance protection schemes and the coordination between various relays in the network was studied and investigated in radiology and meshed operational topologies. Also, in cases of islanded and grid-connected modes. An adaptive distance scheme has been proposed for adequate planning of protection schemes to protect complex networks with multiple distribution sources. The simplified simulated network implemented in NEPLAN represents a benchmark IEC microgrid. The comprehensive results show an effective protection measure for secured microgrid operation.Article History: Received October 18th 2017; Received in revised form May 17th 2018; Accepted July 8th 2018; Available onlineHow to Cite This Article: Saad, S.M., Naily, N.E. and Mohamed, F.A. (2018). Investigating the Effect of DG Infeed on the Effective Cover of Distance Protection Scheme in Mixed-MV Distribution Network. International Journal of Renewable Energy Development, 7(3), 223-231.https://doi.org/10.14710/ijred.7.3.223-231


2020 ◽  
Vol 2020 ◽  
pp. 1-13 ◽  
Author(s):  
Panida Thararak ◽  
Peerapol Jirapong

The flexible operation of microgrids, along with the availability of distributed generation (DG) units, causes a variety of changes in short-circuit current levels, magnitudes, and directions, which has undesirable effects on the operation of protection systems. Conventional protection schemes use typical directional overcurrent relays (DOCRs) with limited operating capability, unable to respond to microgrid operations in the manner of short-circuit current changes. In this paper, a quaternary protection scheme implemented with dual-directional overcurrent relays (dual-DOCR) and a protection control strategy is developed for protecting against faults in microgrids, taking into account the existence of DGs and connection and disconnection of DG units. The optimal dual-DOCRs setting and coordination are formulated as an optimization problem solved by evolutionary programming to minimize the relay operating times. The proposed protection scheme is implemented with a centralized protection control system based on the smart grid concept to increase the adaptability of the dual-DOCRs, which have multiple relay setting groups in accordance with system state changes. The simulation case studies are performed using the IEEE 14-bus test system, which is modified as a meshed microgrid operation. Test scenarios, including possible operations of microgrids, DGs availabilities, and different fault events, are analyzed and discussed. The comparative studies and simulation results show that the proposed scheme provides efficient coordination between the primary and backup relays and increases the responsibility of the protection system, which can be observed from the significant reduction in the relay operating times, resulting in the enhancement of selectivity, sensitivity, and speed of microgrid protection systems.


2014 ◽  
Vol 511-512 ◽  
pp. 1099-1102
Author(s):  
Zhen Bao Sun

Recently, many countries have been pushing for a higher share of renewable energy sources, especially wind, in their generation mix. However, the intermittent and uncertain nature of wind power imposes a limit on the extent it can replace the conventional generation resources. In a high wind penetration scenario, the Battery Energy Storage System (BESS) offers a solution to the grid operation problems. The purpose of this paper is to evaluate the merits of price-based operation of BESS in a real-time market with high wind penetration using frequency-linked pricing. The authors propose a real-time market in which real-time prices are based on the grid frequency. A model for real-time price-based operation of a conventional generator and a BESS is presented. Simulations for different wind penetration scenarios are carried out on an isolated area test system. Wind speed sequence is generated using composite wind speed model. A simplified model of wind speed to power conversion is adopted to observe the impact of increase in wind power generation on the grid frequency and the real-time prices.


Author(s):  
Subramanya Sarma S ◽  
V. Madhusudhan ◽  
V. Ganesh

<p>Reliability worth assessment is a primary concern in planning and designing of electrical distribution systems those operate in an economic manner with minimal interruption of electric supply to customer loads. Renewable energy sources (RES) based Distributed Generation (DG) units can be forecasted to penetrate in distribution networks due to advancement in their technology. The assessment of reliability worth of DG enhanced distribution networks is a relatively new research area. This paper proposes a methodology that can be used to analyze the reliability of active distribution systems (DG enhanced distribution system) and can be applied in preliminary planning studies to compute the reliability indices and statistics. The reliability assessment in this work is carried out with analytical approach applied on a test system and simulated results validate that installation of distributed generators can improve the distribution system reliability considerably.</p>


In this paper,the study of optimal coordination of directional overcurrent relays along with relay communication in HV substations is proposed. The relay coordination problem is non linear.It typically consist of two groups of control variables(Time Dial Settings:TDS and Plug Settings:PS). The purpose of relay coordination is to propose the suitable settings for all releases and ensure the coordination. The differential evolution is employed to solve for solutions of optimal relay coordination. The relay coordination is mainly done to improve selectivity of the relay to particular fault. ETAP is so popular for its capability for modelling of power system networks and analyzing various studies and Real Time simulations.