scholarly journals Study on the Method of Calculating Temperature Rise of Transformer

2020 ◽  
Vol 179 ◽  
pp. 01027
Author(s):  
Tao Li ◽  
Xiaoping Du ◽  
Xuewu Sun ◽  
Yuanyuan Song

The internal temperature of the transformer is a key parameter to measure the thermal state of the transformer. The service life of the transformer generally depends on the life of the insulating material, and high temperature is the main reason why cause insulation aging, this paper studies the temperature rise of transformer winding hot spot temperature for the key, using the neural network forecasting method, forecasts transformer winding hot spot temperature change rule, calculate the transformer internal temperature rise, provide the temperature of the scientific basis for the safe operation of the transformer.

Author(s):  
Shahram Khalil Aria ◽  
Sahar Samsami

In this paper, a developed mathematical model for temperature rise calculation is briefly described. In this model, at first, load loss of a transformer winding with forced directed oil is calculated and the winding temperature rise along the horizontal ducts and vertical ducts is computed. Then hot spot temperature and its exact location is determined. The model can also be used for optimal design of winding in size and cooling. Finally the results are given and compared with experiment values.


2014 ◽  
Vol 1079-1080 ◽  
pp. 492-497 ◽  
Author(s):  
Lun Ma ◽  
Liu Wang ◽  
Ying Ying Sun ◽  
Tao Wan ◽  
Jia Peng Wei ◽  
...  

Oil immersed transformer is an important equipment ofpower system, whose fault is often caused by the aging of insulation. In actualoperation, accurate calculation of the temperature field, especially hot spottemperature of transformer winding, is very important for stabilizing the powergrid operation and extending the transformer life. In order to calculate thetransformer's hot spot temperature accurately, a new method which is based oncomparison of respective advantages of the FEM and FVM is used; we take a31.5MVA transformer as exemple, using the hybrid method of the FEM and the FVM,the three-dimensional temperature field of transformer is calculated. Bycomparing the figures of top oil temperature of transformer monitored by theoperating transformer and the figures calculated by mixed method, the marginerror of the hot spot temperature is only 1.9°C. While the IEEE guidelines formodel calculation results, the calculated results of FEM algorithm and FVMalgorithm results with the monitoring data of standard deviation were as highas 4.6 °C, 3.8 °C and 3.1 °C. The Calculation accuracy is much higher than theaccuracy of the result using IEEE regulatory model, FEM and FVM, proved thatthis mixed method can calculate the internal temperature field of oil immersedtransformer accurately.


2015 ◽  
Vol 51 (3) ◽  
pp. 1-4 ◽  
Author(s):  
Longnv Li ◽  
Shuangxia Niu ◽  
S. L. Ho ◽  
W. N. Fu ◽  
Yan Li

1984 ◽  
Vol PER-4 (6) ◽  
pp. 26-27 ◽  
Author(s):  
W. J. McNutt ◽  
J. C. McIver ◽  
G. E. Leibinger ◽  
D. J. Fallon ◽  
K. A. Wickersheim

2014 ◽  
Vol 1079-1080 ◽  
pp. 510-514
Author(s):  
Yong Qiang Wang ◽  
Jie He ◽  
Lun Ma ◽  
Liu Wang ◽  
Ying Ying Sun ◽  
...  

Thehottest spot temperature (HST) of windings of oil-immersed transformer is animportant factor that affects load capacity and operation life of transformer,and is closely related to the transformer load, top oil and environmenttemperature. HST, when operating at high temperature and overload, may lead totransformer failure which will affect the normal operation of the power system.In order to calculate the transformer hot spot temperature accurately, we takea 33MVA-500KV transformer as an example, and establish a three dimensionalmodel, get its internal temperature distribution based on Fluent simulationsoftware. At last, we comparative and analysis the accuracy of FVM calculation andIEEE guidelines recommend model combined with online monitored values. Theresults show that the FVM method with higher accuracy relative to the IEEEguidelines model, proved that using the FVM can accurately calculate the HST ofoil-immersed transformer.


Author(s):  
Zhengang Zhao ◽  
Zhangnan Jiang ◽  
Yang Li ◽  
Chuan Li ◽  
Dacheng Zhang

The temperature of the hot-spots on windings is a crucial factor that can limit the overload capacity of the transformer. Few studies consider the impact of the load on the hot-spot when studying the hot-spot temperature and its location. In this paper, a thermal circuit model based on the thermoelectric analogy method is built to simulate the transformer winding and transformer oil temperature distribution. The hot-spot temperature and its location under different loads are qualitatively analyzed, and the hot-spot location is analyzed and compared to the experimental results. The results show that the hot-spot position on the winding under the rated power appears at 85.88% of the winding height, and the hot-spot position of the winding moves down by 5% in turn at 1.3, 1.48, and 1.73 times the rated power respectively.


2021 ◽  
pp. 264-264
Author(s):  
Fating Yuan ◽  
Wentao Yang ◽  
Bo Tang ◽  
Yue Wang ◽  
Fa Jiang ◽  
...  

In this paper, the CFD (computational fluid dynamics) model is established for the low voltage winding region of an oil-immersed transformer according to the design parameters, and the detailed temperature distribution within the region is obtained by numerical simulation. On this basis, the RSM (response surface methodology) is adopted to optimize the structure parameters with the purpose of minimizing the hot spot temperature. After a sequence of designed experiments, the second-order polynomial response surface and the SVM (support vector machine) response surface are established respectively. The analysis of their errors shows that the SVM response surface can be better used to fit the approximation. Finally, the PSO (particle swarm optimization) algorithm is employed to get the optimal structure parameters of the winding based on the SVM response surface. The results show that the optimization method can significantly reduce the hot spot temperature of the winding, which provides a guiding direction for the optimal design of the winding structure of transformers.


Author(s):  
S. W. Twaites ◽  
R. F. Murray

It is normal practice when designing electrical machines to design for operation within the maximum temperature limits of the insulation. If part of the winding is not effectively cooled under these conditions, the resulting temperature rise can damage the insulation and seriously reduce the length of operational service of the machine. This paper discusses a method of detecting high-temperature regions within a winding and of estimating the ‘hot spot’ temperature. The investigation has been concentrated on the design associated with a direct water-cooled winding, although the results could be applied generally on other electrical machines.


Sign in / Sign up

Export Citation Format

Share Document