Experimental Study of Inclination on Non-Boiling Regime Spray Cooling

Author(s):  
Yongxian Guo ◽  
Jianyuan Jia ◽  
Weidong Wang ◽  
Shaorong Zhou

Based on the maximum CHF (critical heat flux) criterion, an optimal heat transfer criterion, which is called H criterion, was proposed. Experimental apparatuses were conducted. Distilled water was used as the working fluid. Three different DANFOSS nozzles with cone angles being 54°, 50° and 54° respectively were used. A 30×30mm2 square copper surface was used as the heated surface. Experimental results indicated that the volumetric fluxes were proportioned to P0.5, where P is the pressure drop across the nozzles. The optimal distance between the nozzles and the heated surface were derived. The results indicated that the optimal heat transfer appeared while the outside of the impellent thin spray film inscribed in the square heated surface. Based on the H criterion aforementioned, two DANFOSS nozzles of the three, with cone angles being 54° and 50° respectively, were used to study the temperature distribution of the heated surface while there were spray inclination angles during spray cooling experiments. Distilled water was also used impacting on the 30×30mm2 square copper surface aforementioned and a circular heated copper surface with diameters being 30mm respectively. The heat flux of the surface was kept in constant (about 26–35W/cm2). The inclination angles were 0°, 10°, 20°, 30°, 40° and 50° respectively. Three thermocouples imbedded in the heated surface were used to predict the grads of the temperature of the surface. Experimental results indicated that the temperature and the grads of the temperature of the surface increases first and then decreases with the increase of the inclination angle.

Author(s):  
Nihal E. Joshua ◽  
Denesh K. Ajakumar ◽  
Huseyin Bostanci

This study experimentally investigated the effect of hydrophobic patterned surfaces in nucleate boiling heat transfer. A dielectric liquid, HFE-7100, was used as the working fluid in the saturated boiling tests. Dielectric liquids are known to have highly-wetting characteristics. They tend to fill surface cavities that would normally trap vapor/gas, and serve as active nucleation sites during boiling. With the lack of these vapor filled cavities, boiling of a dielectric liquid leads to high incipience superheats and accompanying temperature overshoots. Heater samples in this study were prepared by applying a thin Teflon (AF400, Dupont) coating on 1-cm2 smooth copper surfaces following common photolithography techniques. Matching size thick film resistors, attached onto the copper samples, generated heat and simulated high heat flux electronic devices. Tests investigated the heater samples featuring circular pattern sizes between 40–100 μm, and corresponding pitch sizes between 80–200 μm. Additionally, a plain, smooth copper surface was tested to obtain reference data. Based on data, hydrophobic patterned surfaces effectively eliminated the temperature overshoot at boiling incipience, and considerably improved nucleate boiling performance in terms of heat transfer coefficient and critical heat flux over the reference surface. Hydrophobic patterned surfaces therefore demonstrated a practical surface modification method for heat transfer enhancement in immersion cooling applications.


Author(s):  
M. Hamayun Maqbool ◽  
Bjo¨rn Palm ◽  
R. Khodabandeh ◽  
Rashid Ali

Experiments have been performed to investigate heat transfer in a circular vertical mini channel made of stainless steel (AISI 316) with internal diameter of 1.70 mm and a uniformly heated length of 245 mm using ammonia as working fluid. The experiments are conducted for a heat flux range of 15 to 350 kW/m2 and mass flux range of 100 to 500 kg/m2s. The effects of heat flux, mass flux and vapour quality on the heat transfer coefficient are explored in detail. The experimental results show that the heat transfer coefficient increases with imposed wall heat flux while mass flux and vapour quality have no considerable effect. Experimental results are compared to predictive methods available in the literature for boiling heat transfer. The correlations of Cooper et al. [1] and Shah [3] are in good agreement with our experimental data.


Author(s):  
Eric A. Silk ◽  
Jungho Kim ◽  
Ken Kiger

Experiments were conducted to study the effects of enhanced surfaces on heat transfer during spray cooling. The surface enhancements consisted of cubic pin fins, pyramids, and straight fins (uniform cross sectional straight fins) machined on the top surface of copper heater blocks. Each had a cross-sectional area of 2.0 cm2. Measurements were also obtained on a heater block with a flat surface for baseline comparison purposes. A 2×2 nozzle array was used with PF-5060 as the working fluid. Thermal performance data was obtained under nominally degassed (chamber pressure of 41.4 kPa) and gassy conditions (chamber with N2 gas at 101 kPa). The results show that the straight fins had the largest enhancement in heat flux. Critical heat flux (CHF) for this surface showed an increase of 55% in comparison to the flat surface for the nominally degassed condition. The cubic pin finned and pyramid surfaces provided slightly more than half the heat flux enhancement (30%–40% greater than the flat surface) of the straight fins. The gassy case showed that the straight fins again provided the largest enhancement (48%) in CHF relative to the flat surface. This was followed by the cubic pin fins, and pyramids which had increases of 31% and 18% respectively. No significant effect was observed in the surface temperature at which CHF occurs for either portion of the study.


Author(s):  
Ramin Soujoudi

This paper investigates application of Method of Lines (MOL) and Inverse Heat Conduction techniques in spray cooling process. A flat face of a heated cylinder is cooled by using a nozzle spray and using room temperature water as a cooling fluid. The numerical analysis is done using MOL to estimate exposed surface temperature, surface heat flux, and convection heat transfer coefficient [3],[4]. Since there is no exact solution to verify the approximation result, for the verification purpose and accuracy of the result, the numerical result from this study is compared to other approximation results with experimental research done by Chen-Lee and Qiao-Chandra [1]. The results illustrate that disparity between the outcome of MOL and the one generated by Chen and Lee’s raw data is very insignificant throughout the whole time domain. This discrepancy between these two estimated results proves that MOL is a very reliable approximation technique compared to other finite element methods which require a finer mesh size and significant amount of calculations[2],[5]. However, comparing the results obtained through MOL with Qiao and Chandra shows that the difference between the estimated heat transfer coefficient and estimated heat flux converges rapidly for the short times of 0 < t < 60, but as the time passes, the MOL approximation results diverge slowly until it reaches its maximum value at ninety seconds, and the variance remains almost constant for the rest of the time period.


Author(s):  
J. Torres ◽  
A. Perdones ◽  
A. Garcia ◽  
F. J. Diez

Thermal control is a major constraint in spacecraft development as increased demand on electronics performance requires large heat dissipation from smaller surfaces which has led to increased challenges for thermal control. Spray cooling has a great amount of application in industrial processes as a heat removal method. It is thought to be the future in thermal management systems in space because of its capability for ‘close’ and accurate control of heat removal. Spray cooling is based on phase change heat transfer generating high heat transfer rates for low superheats. This last term is used to describe the difference in temperature between the heated surface and the cooling fluid. When the temperature of the surface to be cooled rises above the saturation temperature of the fluid splashed to the surface, a phase change occurs at the solid liquid interface during the boiling regime. However, the most interesting phase (regime) is the nucleating boiling where the critical heat flux, CHF, is reached. The CHF is then achieved due to the vapor generation is such as great that the liquid cannot still be in contact with the surface. Thus the heat is transferred through the vapor if there is not enough cold fluid. The thermal conductivity of vapor is lower and so the efficient of the cooling process. This turns out in a decrease on heat flux. Nowadays it is being taken more into account nanofluids as a technique capable of enhancing heat transfer. Nanofluids, a mix of nano-size particles in a base fluid, have been found to have a very high thermal conductivity as compared to the base fluid. In You et al., 2003; Kim et al., 2004a; Moreno et al., 2005 water was used with various Al2O3 particle concentration in a flat plate nucleate pool boiling system. They came across with no change in the heat transfer coefficient but a dramatic enhancement in CHF. They also found that high concentrations can degrade nucleate boiling. The aim of this project is study the effects of spray cooling with suspended nano-particles as an enhanced method for heat transfer removal. The working fluid was water with different concentrations of alumina-oxide particles added. The alumina oxide particles were supplied by Nanophase Technologies (Nano Tek® Alumina Oxide AL-01000-003-025) which had a mean diameter of 60 nm. Three different concentrations were used and the following: .5 g/L, 1 g/L, 2 g/L. Since clumping of particles can affect the heat transfer properties of the droplets, the solution was placed on inside an ultrasonic bath and left there for at least 24 hrs and immediately used in the experiments. Two nozzles were used in this experiment to study a wide range of sauter diameter of droplets. The experiment was carried out using three experimental techniques which looked into different characteristics of spray cooling. In the first mode, the fluid was sprayed onto a copper block heater surface while it was imaged with a high speed camera and synchronized with a high speed Nd-YAG laser. 9 thermocouples were positioned inside the copper block heater, as seen on Figure 1, to measure critical heat flux, while a camera was used to record different impact properties and the influence of nano-particles. Some of these properties were pool buildup size, spread, and duration of pool. For the second imaging technique, the spray on the heated surface was also considered to be an impinging jet, so to visualize the flow of this jet and how the heated surface affected it, PIV (Particle Image Velocimetry) was used in the study. A third imaging technique was used to study the droplet behavior when in contact with a heated surface. A transparent glass heater made of aluminum silicate glass and coated with an ITO (indium tin oxide) film was used as the heater. The size of the drops had an average diameter of 2.38 mm. When compared to the copper block study, this method allows images to be taken from directly below the clear glass heater. Furthermore, these images allow for a clear edge detection of drops as they spread on the surface and what characteristics they develop when the droplets have different concentrations of nanoparticles, as seen on Figure 2. The experiment used a pulsed laser to provide the background illumination. This project is a continuing research project.


2015 ◽  
Vol 137 (2) ◽  
Author(s):  
Tong-Bou Chang

For spray cooling using nanofluid as the working fluid, a nano-adsorption layer is formed on the heated surface and affects the heat transfer performance of the cooling system. This study performs an experimental investigation into the formation of this nano-adsorption layer and its subsequent effects on the spray heat transfer performance of a cooling system using Al2O3–water nanofluid as the working fluid. The experiments consider four different nanoparticle volume fractions (i.e., 0 vol. %, 0.001 vol. %, 0.025 vol. %, and 0.05 vol. %) and two different surface roughnesses (i.e., 0.1 μm and 1.0 μm). The experimental results show that the 0.001 vol. % nanofluid yields the optimal heat transfer performance since most of the nanoparticles rebound from the heated surface directly on impact or are washed away by subsequently arriving droplets. The surface compositions of the spray-cooled specimens are examined using scanning electron microscopy (SEM) and energy-dispersive X-ray spectroscopy (EDS). The results reveal that for all of the nanofluids, a nano-adsorption layer is formed on the surface of the spray-cooled test pieces. Moreover, the layer thickness increases with an increasing nanoparticle concentration. A greater nano-adsorption layer thickness not only results in a higher thermal resistance but also reduces the effect of the surface roughness in enhancing the heat transfer performance. In addition, the nano-adsorption layer absorbs the nanofluid droplets under the effects of capillary forces, and therefore reduces the contact angle, which induces a hydrophilic surface property.


Author(s):  
Sai Sujith Obuladinne ◽  
Huseyin Bostanci

Two-phase spray cooling has been an emerging thermal management technique offering high heat transfer coefficients (HTCs) and critical heat flux (CHF) levels, near-uniform surface temperatures, and efficient coolant usage that enables to design of compact and lightweight systems. Due to these capabilities, spray cooling is a promising approach for high heat flux applications in computing, power electronics, and optics. The two-phase spray cooling inherently depends on saturation temperature-pressure relationships of the working fluid to take advantage of high heat transfer rates associated with liquid-vapor phase change. When a certain application requires strict temperature and/or pressure conditions, thermophysical properties of the working fluid play a critical role in attaining proper efficiency, reliability, or packaging structure. However, some of the commonly used working fluids today, including refrigerants and dielectric liquids, have relatively poor properties and heat transfer performance. In such cases, utilizing binary mixtures to tune working fluid properties becomes an alternative approach. This study aimed to conduct an initial investigation on the spray cooling characteristics of practically important binary mixtures and demonstrate their capability for challenging high heat flux applications. The working fluid, water/2-propanol binary mixture at various concentration levels, specifically at x1 (liquid mass fraction of 2-proponal in water) of 0.0 (pure water), 0.25, 0.50, 0.879 (azeotropic mixture) and 1.0, represented both non-azeotropic and azeotropic cases. Tests were performed on a closed loop spray cooling system using a pressure atomized spray nozzle with a constant liquid flow rate at corresponding 20°C subcooling conditions and 1 Atm pressure. A copper test section measuring 10 mm × 10 mm × 2 mm with a plain, smooth surface simulated high heat flux source. Experimental procedure involved controlling the heat flux in increasing steps, and recording the steady-state temperatures to obtain cooling curves in the form of surface superheat vs heat flux. The obtained results showed that pure water (x1 = 0.0) and 2-propanol (x1 = 1.0) provide the highest and lowest heat transfer performance, respectively. At a given heat flux level, the HTC values indicated strong dependence on x1, where the HTCs depress proportional to the concentration difference between the liquid and vapor phases. The CHF values sharply decreased at x1≥ 0.25.


Author(s):  
Eric A. Silk ◽  
Jungho Kim ◽  
Ken Kiger

Experiments were conducted to study the effects of enhanced surface structures on heat flux using spray cooling. The surface enhancements consisted of cubic pin fins machined on the top surface of copper heater blocks. The structure height, pitch, and width were parametrically varied. Each copper block had a projected cross-sectional area of 2.0 cm2. Measurements were also obtained on a heater block with a flat surface for baseline comparison purposes. A 2×2 nozzle array was used with PF-5060 as the working fluid. Thermal performance data was obtained under nominally degassed (chamber pressure of 41.4 kPa) and gassy conditions (chamber with N2 gas at 101 kPa) with a bulk fluid temperature of 20.5°C. Results for both the degassed and gassy cases show that structure width and separation distance have a dominant effect upon the heat transfer for the size ranges used. Cubic pin fin height had little impact upon heat flux. The highest critical heat flux (CHF) attained for any of the surfaces was 121 W/cm2, giving an enhancement of 51% relative to the flat surface case under nominally degassed conditions. The highest CHF in the gassy case was 149 W/cm2, giving an enhancement of 38% relative to the flat surface case.


Author(s):  
Frank Pyrtle ◽  
Alberto D. Sato

Experiments were performed to determine heat transfer characteristics of water sprays impacting a flat, inverted surface. Using a compressed gas tank to provide motive force in an open loop spray cooling system, droplet sprays were produced without the assistance of an atomizing gas stream. A range of droplet volumetric fluxes was produced for cooling the inverted heated surface using a full-cone spray nozzle. Heat transfer curves were plotted in the form of heat flux as a function of wall temperature difference, for volumetric flow rates up to 627 mL/min, dissipating up to 451 W/cm2. Heat transfer coefficients were also determined as functions of heat flux. The results were compared to prior data for standard, downward spraying onto heated surfaces.


Author(s):  
Gilberto Moreno ◽  
Seung M. You ◽  
Erlendur Steinthorsson

In this study experiments were performed to evaluate the spray cooling performance of three different spray nozzles using gassy-subcooled (∼Tsub = 31°C) FC-72 as the working fluid. The three different nozzles tested can be characterized as a single hollow cone spray nozzle (Nozzle A), 2×2 jet array spray nozzle (Nozzle B) and a 4×4 jet array spray nozzle (Nozzle C). For all tests, a 10×10 mm polished (600 grit) copper surface was utilized as the heater and tests were carried out at near atmospheric pressure conditions. All three nozzles were tested at various flow rates and nozzle-to-heater distances and the results were compared. Results show that changing the nozzle-to-heater distance affects heat transfer rates more than critical heat flux (CHF). The spray boiling curves for all three nozzles were similar with Nozzle C, for some cases, demonstrating the highest heat transfer rates. The disparity in CHF values between the various nozzles was more apparent. Compared at an equivalent flow rate, Nozzle C consistently produced CHF values which were higher than those of the other nozzles. Some common trends observed for all nozzles are, increasing flow rate increases heat transfer rates and critical heat flux (CHF) but decreases nozzle efficiency.