scholarly journals Calculation of two-phase ground fault current with consideration of equipment grounding specifications

2018 ◽  
Vol 19 (12) ◽  
pp. 468-473
Author(s):  
Aleksiej Kosjakow ◽  
Aleksandr Suhoguzow

The article describes ways of calculating two-phase ground fault current in electrical networks with isolated neutral for needs of calculating thermal resistance in equipment's grounding elements. Grounding resistance and metal resistance of high-voltage equipment are added to the existing methods of short circuit currents calculation.

2020 ◽  
Author(s):  
◽  
Sindisiwe Cindy Malanda

A multiterminal HVDC system includes the connection of different HVDC terminals to a common grid. Most of the MTDC networks are realized in voltage source converter (VSC) high voltage direct current (HVDC). Over long distances, HVDC transmission is preferred to high voltage direct current (HVAC). Furthermore, HVDC is subjected to minimal harmonics oscillation problems due to the absence of frequency. HVDC enables the interconnection of systems at different frequencies, and the system becomes free of angular stability problems. VSCs employ insulated gate bipolar transistors (IGBTs) switches, and High-frequency pulse width modulation is used to operate the IGBTs in order to achieve high-speed control of active and reactive power. The growth of MTDC networks may require a new type of VSCs topology, which is resilient and efficient to dc and ac network fault. This research investigation focuses on the transient dc-side fault analysis in a two-level Monopolar VSC- Based Multi-Terminal HVDC Scheme consisting of four asynchronous terminals sharing a rated 400kV DC-grid was carried out in PSCAD software. During dc-side fault analysis, a pole-to-ground fault was taken into consideration as it’s more likely to occur, although it is less severe compared to pole-to-pole. The converters are interconnected through 100 km dc cables placed 0.5 gm apart and at a depth of 1.5 m underground. It was observed that during the steady-state analysis, the dc voltage in the grid was maintained at the rated value 400 kV, the currents measured at the converters bus was 0.5 kA, and the current flowing through the cables was 0.25 kA. Under the fault condition, the dc voltage drop needs to be maintained to a closed range to avoid the grid to collapse. The voltage droop technique was incorporated in the dc voltage controller to keep the dc voltage at the narrow range. Depending on the value and nature of ground fault resistance, the fault current magnitude varies, and distance variation along the cable has a significant contribution in the fault current. It is observed that fault close to the converter (5 km’s measured 9 kA) results in high fault currents compared to fault away from the converter (50 km’s measured 7.8 kA). The protection design of the VSC needs to be able to detect whether its ground fault or short circuit since the location of the fault needs to be identified and repaired. Another observation made when the fault is inserted 50 kms away from the converter, meaning the fault is at the center of the two converters, the outcome results in high currents in both converters. The isolation of the fault should be fast and selective as the critical time is very short. The dc circuit breakers are mostly recommended to be used as primary protection; however, different protection techniques need to be incorporated with dc circuit breaker in order to quickly identify, select and reliable isolate the faulted line. Moreover, the protection should be able to isolate the line before the fault reaches the maximum fault current to avoid the damage in the converter components.


2014 ◽  
Vol 960-961 ◽  
pp. 891-895
Author(s):  
Xu Zheng ◽  
Jiang Hong Wang ◽  
Mei Li ◽  
Shuang Zhao ◽  
Bu Han Zhang ◽  
...  

Ultra-high voltage (UHV) projects are making power system growing lager and resulting in sharp increase of short circuit currents in some area especially in the vicinity of UHV access points. The paper presented the damage of short circuit current increases and common methods to limit fault current. Taking the construction and development of UHV grid in a province of central China as background, the over short circuit currents in 500kV Grid within UHV were showed and several countermeasures including choosing proper UHV access scheme, implementing UHV substation lower voltage bus partition running, installing reactors, optimizing power grid network based on UHV connection point were proposed and then verified by PSASP simulation. The results show those measures are useful to reduce the short circuit current to a reasonable level.


Author(s):  
Aleksandr S. Serebryakov ◽  
Vladimir L. Osokin ◽  
Sergey A. Kapustkin

The article describes main provisions and relations for calculating short-circuit currents and phase currents in a three-phase traction transformer with a star-triangle-11 connection of windings, which feeds two single-phase loads in AC traction networks with a nominal voltage of 25 kilovolts. These transformers provide power to the enterprises of the agro-industrial complex located along the railway line. (Research purpose) The research purpose is in substantiating theoretical equations for digital intelligent relay protection in two-phase short circuits. (Materials and methods) It was found that since the sum of instantaneous currents in each phase is zero, each phase of the transformer works independently. We found that this significantly simplifies the task of analyzing processes with a two-phase short circuit. In this case, the problem of calculating short-circuit currents in the traction network can be simplified by reducing it to the calculation of an ordinary electric circuit with three unknown currents. (Results and discussion) The article describes equations for calculating short-circuit resistances for one phase of the transformer when connecting the secondary winding as a star or a triangle. The currents in the phases of the transformer winding at short circuit for the star-triangle-11 and star-star-with-ground schemes are compared. It was found that when calculating short-circuit currents, there is no need to convert the secondary winding of the traction transformer from a triangle to a star. (Conclusions) It was found that the results of the research can be used in the transition of relay protection systems from electromagnetic relays to modern high-speed digital devices, which will increase the operational reliability of power supply systems for traction and non-traction power consumers.


2018 ◽  
Vol 18 (4) ◽  
pp. 162-167 ◽  
Author(s):  
Miroslav Gutten ◽  
Daniel Korenciak ◽  
Matej Kucera ◽  
Richard Janura ◽  
Adam Glowacz ◽  
...  

Abstract The authors describe experimental and theoretical analyses of faults of power transformer winding. Faults were caused by mechanical effect of short-circuit currents. Measurements of transformer were carried out in high-voltage laboratory. Frequency and time diagnostic methods (method SFRA - Sweep Frequency Response Analysis, impact test) were used for the analyses. Coils of transformer windings were diagnosed by means of the SFRA method and the time impact test. The analyzed methods had a significant sensitivity to a relatively small deformation of coil. In the analysis a new technique for analyzing the effects of short-circuit currents is introduced. This technique is developed for high-voltage transformers (different types of power). The proposed analyses show that it is necessary to analyze the value of short-circuit current. Short-circuit current represents a danger for the operation of the power transformer. The proposed approach can be used for other types of transformers. Moreover, the presented techniques have a potential application for fault diagnosis of electrical equipment such as: transformers and electrical machines.


2013 ◽  
Vol 389 ◽  
pp. 1089-1095
Author(s):  
Jun Zhen Peng ◽  
Kun Nan Cao ◽  
Da Da Wang ◽  
Meng Song ◽  
Nan Nan Hu ◽  
...  

As one of the most applicable to high-voltage network superconducting fault current limiterSCFCL(saturated core superconducting fault current limiter) ,which use of core saturation properties can be achieved the current-limiting function without delay ,will be the most widely applied in the future,By analyzing the working principle of SCFCL,this paper use of PSCAD and finite element analysis software Ansoft to build the 500kV\/3150A grade SCFCL model and accurate calculation coil self-inductance and mutual inductance, the harmonic of each size and analyzed its Impedance characteristic on the different external parameters,The results show that SCFCL has a excellent performance for high voltage power network short-circuit current limitation, and provides important reference for design.


2020 ◽  
Vol 3 (1) ◽  
pp. 30-40
Author(s):  
I Nengah Sunaya ◽  
I Gede Suputra Widharma

This research had done base on case study in the feeder of substation 20 kV Jababeka. Existing data showed that condition is well with not too long differential, over all setting on the Overcurrent Relay (OCR) – Ground Fault Relay (GFR) in the field is well. From calculated result can be seem that current of short circuit disturb is influenced by distance between disturbance points. Using over current relay has important purpose in the protection of electricity system. The qualification need setting minimum time of over current relay in the feeder not less than 0.3 second. This consider to the relay will not in trip condition in rush current from distribution transformator that has been connected in the distribution system when the feeder starts operated. Starting time for relay in the feeder is faster than work time in the incoming side with average time about 0.4 second for one phase disturbance side. But for three phase and two phase disturbance side, work time relay has interval time about 0.4 second and than increase with average increament about 0.1 second when transmission line is longer (from distance aspects about 0%, 25%, 50%, 75% and 100%).


2019 ◽  
Vol 6 (2) ◽  
pp. 140-143 ◽  
Author(s):  
S. A. Averyanova ◽  
E. Tonkonogov

A comprehension of the dielectric strength recovery processes during the interruption of short-circuit currents in the high-voltage SF<sub>6</sub> gas-blast circuit breakers is necessary for their modernisation in order to increase the rated voltage and short circuit breaking current per one break. This paper presents numerical results of the turbulence effects on the interruption ability in the SF<sub>6</sub> extinguishing arc chamber.


This chapter sheds light on the following: TT system (earthed neutral), automatic disconnection for TT system, TN system (exposed conductive parts connected to the neutral), TN-C system, TN-S system- TN-C-S system, IT system (isolated or impedance-earthed neutral), IT system (impedance-earthed neutral), grounding transformer connection and design, grounding of industrial and commercial generators, Zigzag grounding transformer earthed systems (solid grounding, resistance grounding, reactance grounding, resonant grounding (ground-fault neutralizer), location of system grounding points selection and grounding locations specified by the NEC and multiple power sources. The chapter contains also the different methods used in determining the levels of short circuit current. It contains also details about the grounding through resistances for transformers and generators and reactances for overhead transmission lines.


Sign in / Sign up

Export Citation Format

Share Document