scholarly journals Decreasing the Tendency of Water to Form Scale and Corrosion in Cooling Towers – South Refineries Company (SRC) – Iraq

2021 ◽  
Vol 11 (2) ◽  
pp. 15-29
Author(s):  
Thabit Abbas ◽  
Qays M. Ammouri ◽  
Thikra Shihab ◽  
Ola Jabur

Scale formation and corrosion phenomena are major technical problems at Basra Refinery/ South Refineries Company (SRC). These technical problems are concentrated in cooling towers which are used to supply cooling water to the processing units. The Scales and corrosion products precipitate inside cooling units, heat exchangers and pipeline networks affecting negatively efficiency of refinery’s equipment. In this work, a real plant data was collected from four cooling towers which is supplied the coolant to the crude distillation units of the refinery and also from the raw water supplier. The collected data was fitted by Langelier model to predict the tendency of cooling water for scale forming and activation of corrosion. The obtained result shows that the cooling water has a tendency to form scale (CaCO3 Precipitation) at cooling tower units. Also the feed water has the same tendency for scale forming.After analyzing the LSI (Langelier Saturation Index) results, the research team recommends the particular company to overcome this problem by installing a Reverse Osmosis (RO) plant for treating raw water to decrease the concentrations of total dissolved solids (TDS) which result scale and corrosion in the parts of cooling tower as an option to solve the problem.

2021 ◽  
Vol 11 (2) ◽  
pp. 15-29
Author(s):  
Thabit Abbas ◽  
Qays Muthna ◽  
Thikra Shihab ◽  
Ola Jabur

Scale formation and corrosion phenomena are major technical problems at Basra Refinery/ South Refineries Company (SRC). These technical problems are concentrated in cooling towers which are used to supply cooling water to the processing units. The Scales and corrosion products precipitate inside cooling units, heat exchangers and pipeline networks affecting negatively efficiency of refinery’s equipment. In this work, a real plant data was collected from four cooling towers which is supplied the coolant to the crude distillation units of the refinery and also from the raw water supplier. The collected data was fitted by Langelier model to predict the tendency of cooling water for scale forming and activation of corrosion. The obtained result shows that the cooling water has a tendency to form scale (CaCO3 Precipitation) at cooling tower units. Also the feed water has the same tendency for scale forming.After analyzing the LSI (Langelier Saturation Index) results, the research team recommends the particular company to overcome this problem by installing a Reverse Osmosis (RO) plant for treating raw water to decrease the concentrations of total dissolved solids (TDS) which result scale and corrosion in the parts of cooling tower as an option to solve the problem.


2013 ◽  
Vol 12 (3) ◽  
pp. 231-238
Author(s):  
Teresa Szymura ◽  
Wojciech Adamczyk

Corrosion testing was performed on structural steel of a cooling tower in the environment of cooling water containing ammonium sulfates and ammonium chloride. The test were performed using gravimetric and electrochemical methods with the application of a potentiostat. The analyses clearly showed that the corrosion rate is higher in solutions that contain ammonium sulfate and that the S235JRG2 steel exhibits higher corrosion resistance in this environment.


Author(s):  
Hanno C. R. Reuter ◽  
Detlev G. Kro¨ger

In cooling towers packed with trickle or splash fills, which have almost isotropic or anisotropic flow resistance, the air flow through the fill is oblique or in cross-counterflow to the water flow, particularly at the cooling tower inlet when the fill loss coefficient is small or when the fill hangs down into the air inlet region. This results that the fill Merkel number or transfer characteristic for cross-counter flow is between that of purely counter- and crossflow fills. When using CFD to model natural draught wet-cooling tower performance for isotropic fill resistance, two- or three-dimensional models are therefore required to determine fill performance. In this paper, the governing fundamental partial differential equations are derived in cylindrical and Cartesian co-ordinates to determine the cooling water temperature, water evaporation rate, air temperature and air humidity ratio in two-dimensional cross-counterflow fills for both saturated and supersaturated air. To solve these equations, a relation is proposed to determine Merkel numbers for oblique air flows by linear interpolation and extrapolation of purely cross- and counterflow Merkel numbers in terms of the air flow angle. This model is compared to analytical Merkel numbers obtained for different air flow angles using a single drop trajectory model. A linear upwind computational model and an Eulerian FLUENT® model are developed to evaluate fill performance characteristics from test data and to model fill performance in cooling towers respectively. The results of these two models are compared and verified with a FLUENT® Euler-Lagrange model.


Author(s):  
David Werth ◽  
Matthew Havice

Pump intake structures are a necessary component of the cooling water systems for power plants, process and manufacturing facilities, flood control and water/wastewater applications. Large cooling water systems often use substantial sea / river water intakes or cooling towers to provide the required cooling of the process or circulating water. These structures can be very large and often house multiple pump with capacities ranging in size from a few hundred m3/hr to 60,000 m3/hr or more. With such large flow rates care must be taken to ensure uniform flow to the pump to limit vortex activity, vibration, flow induced cavitation and performance problems. In many cases, a physical hydraulic model study is conducted to evaluate the overall approach flow and the performance of the intake. This paper presents a synopsis of several recent physical model studies and a review of recurring problems associated with common design features. This paper takes a closer look at stop log support walls, an intake design feature common to seawater intakes. This wall is often used to minimize the height of the stop logs. In applications with large variations of water level, such as a seawater intake, there are times when the support walls are submerged significantly, resulting in significant flow disturbances. A feature common to cooling towers is the use of 90-degree suction elbows to supply horizontal pumps. A review of short radius vs. long radius elbow performance is presented. Cooling towers often have another common feature which is a significant difference in depth between the cooling tower basin and the pump sump. This results in typical shallow basins and deeper sumps. A common problem is the utilization of minimum pump submergence to set the water levels without reference to the basin invert elevation. A discussion of choked flow conditions in cooling towers is presented. A final discussion is presented regarding cross-flow and the use of concentrated supply channels in cooling tower applications to facilitate the isolation of individual tower cells. This paper presents a synopsis of several recent physical model studies and a review of recurring problems associated with common intake design features. The results of several model studies are presented to demonstrate the negative impacts that these common intake features have on approach flow conditions. The intent of the paper is to provide the design engineer some additional guidance not offered in industry guidelines or standards with the hope of avoiding common problems which can be costly and difficult to remediate after the intake has been constructed.


Proceedings ◽  
2019 ◽  
Vol 16 (1) ◽  
pp. 3
Author(s):  
Iwona Skoczko ◽  
Ewa Szatyłowicz

The aim of the study was assessment of groundwater stabilization. Corrosive water effects on metals include complex electrochemical and biochemical processes. None of the water components remain indifferent to the metal and can accelerate or delay its corrosion. On the basis of the conducted tests of water samples, the aggressiveness and corrosivity indicators were calculated. Conducted research included analyses of raw and treated water. Raw water was taken as groundwater. Then it was treated in individual and complex processes such as aeration, filtration and ion exchange. Water aggressiveness and corrosion level were introduced by the Langelier Saturation Index (LSI), the Ryznar Stability Index (RI), the Larsoni–Skold Index (LI) and the Singley Index (SI). Obtained results proved that used water treatment processes must be improved through additional aeration and filtration with a dolomite bed. A simple system typical for industrial water is not enough to reach stable water because of remaining aggressiveness and corrosion.


2008 ◽  
Vol 31 (1) ◽  
pp. 118-126
Author(s):  
O.K. Kaunde

Cooling towers are one of the largest heat and mass transfer devices that are in common use. A novel type of cooling tower has been proposed in which air flow rate into the tower is drawn by ejector action of sprays instead of fans as is done in conventional mechanical forced or induced draft cooling towers. This novel design offers the potential of savingthe energy cost for driving the fan. The paper presents mathematical models for momentum transfer which is the driving force causing the entrainment of air. Also the heat transfer model for co-current flow of liquid and gas in the tower has been presented. The liquid to gas ratio tend to decrease as liquid rate increases. The ratio attained in the experimentallaboratory tower was 3.3, correspondingly the Momentum transfer efficiency for the tower was 60% and was the highest. Experiments for cooling water initially at 45 o C to final water temperature 27 o C showed that the cooling tower efficiency was 54% and number of transfer unit 0.8.


2015 ◽  
Vol 766-767 ◽  
pp. 505-510 ◽  
Author(s):  
J. Jayaprabakar

The cooling water system is the industry’s primary way of conserving water. Modern water cooling towers were invented during the industrial age to dissipate heat when natural cooling water sources were available. The origin of cooling towers made the plant site selection independent of the availability of water source. The development of new, high efficiency film fills produced from light weights, flame retarded PVC reduces the size and weight of cross flow cooling towers. Today’s cooling tower combine the latest advanced materials to achieve the optimum balancing of High corrosion resistance, product durability and cost. Based on their specific functions, cooling tower components are designed using the materials with the best combination of corrosion resistance and physical properties. In this work, the coefficient of performance is determined by using Simpson’s rule and the performance of cooling tower at various L/G ratios is evaluated. The optimum approach of the tower is calculated.


Author(s):  
H. C. R. Reuter ◽  
D. G. Kröger

In cooling towers packed with trickle or splash fills, which have anisotropic flow resistance, the air flow through the fill is oblique or in cross-counterflow to the water flow, particularly at the cooling tower inlet when the fill loss coefficient is small or when the fill hangs down into the air inlet region. This results in that the fill Merkel number or transfer characteristic for cross-counter flow is between that of purely counter- and crossflow fills. When using CFD to model natural draught wet-cooling tower performance for isotropic fill resistance, two- or three-dimensional models are therefore required to determine fill performance. In this paper, the governing fundamental partial differential equations are derived in cylindrical and Cartesian coordinates to determine the cooling water temperature, water evaporation rate, air temperature, and air humidity ratio in two-dimensional cross-counterflow fills for both saturated and supersaturated air. To solve these equations, a relation is proposed to determine Merkel numbers for oblique air flows by linear interpolation and extrapolation of purely cross- and counterflow Merkel numbers in terms of the air flow angle. This model is compared to analytical Merkel numbers obtained for different air flow angles using a single drop trajectory model. A linear upwind computational model and an Eulerian FLUENT® model are developed to evaluate fill performance characteristics from test data and to model fill performance in cooling towers, respectively. The results of these two models are compared and verified with a FLUENT Euler–Lagrange model, showing minor deviations.


Energies ◽  
2021 ◽  
Vol 14 (19) ◽  
pp. 6412
Author(s):  
Zbigniew Buryn ◽  
Anna Kuczuk ◽  
Janusz Pospolita ◽  
Rafał Smejda ◽  
Katarzyna Widera

The paper presents the results of measurements and calculations concerning the influence of weather conditions on the operation of wet cooling towers of 905 MWe units of the Opole Power Plant (Poland). The research concerned the influence of temperature and relative humidity of air, wind and power unit load on the water temperature at the outlet from the cooling tower, the level of water cooling, cooling efficiency and cooling water losses. In the cooling water loss, the evaporation loss stream and the drift loss stream were distinguished. In the analyzed operating conditions of the power unit, for example, an increase in Tamb air by 5 °C (from 20–22˚C to 25-27˚C) causes an increase in temperature at the outlet of the cooling tower by 3-4˚C. The influence of air temperature and humidity on the level of water cooling ΔTw and cooling efficiency ε were also found. In the case of ΔTw, the effect is in the order of 0.1-0.2˚C and results from the change in cooling water temperature and the heat exchange in the condenser. The ε value is influenced by air temperature and humidity, which determine the wet bulb temperature value. Within the range of power changes of the unit from 400 to 900 MWe, the evaporated water stream mev, depending on the environmental conditions, increases from 400-600 tons/h to the value of 1000-1400 tons/h. It was determined that in the case of the average power of the unit at the level of 576.6 MWe, the average values of the evaporation and drift streams were respectively 0.78% and 0.15% of the cooling water stream. Using statistical methods, it was found that the influence of wind on the level of water cooling, cooling efficiency and cooling water losses was statistically significant.


Author(s):  
Amir Hossein Beigi ◽  
Ali Mousavi ◽  
Hani Sadr Hosseini

Cooling towers are the main parameters for oil and gas industries. The water that circulates the system will pass through heat exchangers and surface condenser of compressor. Cooling towers operate outside; there is a high chance of debris entering the system and water via wind which therefore could lead to fouling, scaling and corrosion. In order for cooling towers to perform at high efficiency, the water has to be clean. Filtration package are the key for solving this matter. In this thesis, a new filtration package for Marjan petrochemical company has been proposed. In this design the blow down water of the cooling tower will be filtered via first a side stream filtration unit which will decrease the TSS of the water and then enters a Reverse Osmosis package which will reduce the TDS of the water. From the Hysys simulation, it has been proven that this system will produce 63 m3/hr pure water and 37 m3/hr brain water. The compositions of these water are 97% pure water and 3% debris, 96% debris and 4% water respectively. This showed that the filtration package decreased the TDS of the water to 4 ppm which is the specification of the make-up water of cooling tower. Financially, when there is no package installed, Marjan has to send COC and POC waters to Mobin Company for filtrations and then buy the RO water.


Sign in / Sign up

Export Citation Format

Share Document