scholarly journals Methodology for managing equipment repairs in oilfield electrical networks

Author(s):  
Vladimir Levin ◽  
◽  
Nikolay Guzhov ◽  
Natalya Chernenko ◽  
Ammar Yahya ◽  
...  

An innovative methodology for managing repairs in distribution networks and power supply systems for oilfield facilities is proposed in this paper. The methodology makes it possible to select optimal solutions in accordance with the priority management goal by formalizing a risk-based model for planning maintenance and repair (M&R) of electrical equipment with a "condition-based maintenance" strategy. One of the main options in the complex of M&R management tasks is an adaptive model of the technological map for the repairs of power facilities, formed in compliance with a number of key principles. The developed model allows you to optimize the volume and complexity of repairs of electrical equipment of a certain type based on the minimum composition of technological operations necessary to eliminate the identified defects. Detection of defects in electrical equipment is achieved by using methods of technical diagnostics and non-destructive testing. In this case, each of the defects is recorded in the defect statement for the object, with the determination of the degree of criticality and fixing a specific type of corrective action. Optimal prioritization of electrical equipment repairs is performed in accordance with the minimum risk function under current restrictions on reliability (an equipment technical condition index) and available resources (total maintenance costs). The originality of the implementation of a key risk event – a power supply failure of an oilfield facility provides calculating the probability and severity of the consequences of an electrical equipment failure taking into account its technical condition and features of the power supply scheme. The given example illustrates the effectiveness of the proposed approach and emphasizes the validity of optimal decisions. The key components of the developed methodology have found practical application in the conditions of real operation of the equipment of oilfield facilities.

2021 ◽  
Vol 24 (1) ◽  
pp. 69-72
Author(s):  
SKRYPNYK S. ◽  

In the current global economic crisis and acute shortage of energy resources, increasing importance is attached to energy saving measures, economical and careful consumption of raw materials, materials, electricity and heat, environmental safety of industrial production. During the reconstruction of existing power supply systems of industrial enterprises, modern progressive solutions should be considered and implemented, morally and physically obsolete electrical equipment should be replaced, namely the introduction of new electrical equipment for transition from 6/10 kV to 20 kV in Ukrainian power systems. It is also necessary to pay attention to the improvement of power supply circuits and distribution networks, the implementation of complex automation of complex technological processes, rational compensation of reactive power at all levels of power supply systems. In the power system, the main transport link is the power line. Power lines (transmission lines) are long conductors suspended at a safe distance from the ground overhead lines (overhead lines) or cable lines (overhead lines) in which conductors are insulated from each other and from the environment and protected by insulation and armor electricity. Power lines are the most massive elements of the power supply system, they connect the individual nodes of its circuit. Longitudinal and transverse parameters are distinguished in alternative schemes. The load current flows through the longitudinal parameters, voltage is applied to the transverse ones. The replacement circuit of the electrical network consists of replacement circuits of the following elements: power lines, transformers, reactors, capacitors, loads, power sources. Calculating the steady-state modes of power systems, the substitution schemes of the elements are given in a single-line design, because the parameters of all phases are symmetrical. In local and local electrical networks with a relatively short length and low rated voltage, the conduction currents are small compared to load currents. Therefore, in typical electrical calculations of these networks, the capacitive conductivity of the lines is not taken into account. However, for these networks, the accounting of capacitive conductivities is necessary when considering some modes, the existence of which in itself is due only to the presence of capacitive conductivities. For example, the mode of single-phase ground fault in a network with isolated or compensated neutral or analysis of the modes of operation of neutrals of electrical networks of different voltage classes cannot be performed without taking into account the capacitive conductivity of these networks. When switching the power system of Ukraine to the nominal voltage of 20 kV, it should be taken into account that the transmission line will be replaced in the sections of both the overhead power line and cable power line, namely 35, 10, 6 kV. The replacement scheme must describe all the characteristics and properties of the elements of cable and overhead lines in accordance with real conditions. Thus, it is not expedient to use simplified substitution circuits that neglect energy parameters and properties of conductors to study the parameters of transmission lines. The use of a complete "P" -shaped scheme for the analysis of the parameters of transmission lines and transmission lines for a voltage of 20 kV is the basis of mathematical modeling of the transmission system in the distribution networks of our country.


2021 ◽  
Vol 2061 (1) ◽  
pp. 012131
Author(s):  
O N Litskevich ◽  
A P Litskevich

Abstract This article solves the problem of a quantitative assessment of the occurrence of destruction in the intersystem interactions of the transport system and the electrical system of the seaport, in the conditions of the technological process in the seaport, which indicates its significant impact on the electrical system, as a result of which the reliability of the berthing power line is significantly reduced. The intersystem interactions that occur during the implementation of the technological process, as experience shows, are the causes of critical situations that occur at the border of areas of different physical nature, and the consequences are recorded, in the case under consideration, in the electrical system. A mathematical model describing intersystem destruction in quantitative form is presented in this paper using a logical-probabilistic model that reflects internal and external relationships. In the object under study, the destructive cause (collision) and the consequence (accumulation of electrical damage in the insulation of the cable line) are in the same object (the mooring power supply unit), and this is limited to the effects of intersystem destruction. In such a statement, the object of power supply of the technological process and equipment is considered as a composite object containing a cable line and an electric contact column. The problem being formulated is an important and relevant scientific task, which includes not only the question of identifying the causes of increased electrical wear of the power line, but also the development of methods for obtaining quantitative results, and in practical terms also involves the diagnosis of the technical condition of electrical equipment and timely preventive maintenance.


Vestnik MGTU ◽  
2020 ◽  
Vol 23 (4) ◽  
pp. 345-353
Author(s):  
E. I. Gracheva ◽  
A. N. Gorlov ◽  
A. N. Alimova

Determination of the main characteristics of the topology and technical condition of equipment underoperating conditions is necessary for analyzing and assessing power and electricity losses in intrashoplow-voltage industrial power supply networks. A comparative analysis of the technical characteristicsof automatic circuit breakers VA57-31 (KEAZ), NSX100 TM-D (Schneider Electric), DPX3 160 (Legrand), Tmax XT1 TMD (ABB) has shown that the main technical parameters of the machines are close in their values. At that it has been found out that automatic switches of the BA57-31 series have the lowest value of power losses per pole (7.5 W), whereas the automatic switches of the Tmax XT1 TMD series have the highest value (10 W). Thus, under the operating conditions of the equipment, the lowest value of power and electricity losses is characteristic of low-voltage electrical networks with installed circuit breakers of the BA57-31 series, and the highest value of losses is noted in in-shop systems with installed circuit breakers Tmax XT1 TMD. Using catalog data, the dependences of active power losses in circuit breakers on rated currents have been established; the algorithms have been developed and the obtained dependences have been modeled using approximating functions. The standard deviation of the compiled approximating functions has been calculated. Analytical expressions of the dynamics of power losses per pole have been determined as a function of the rated current. The graphical dependences of the investigated parameters of low-voltage equipment have been presented. The developed models are recommended to be used to increase the reliability of the assessment and refinement of the amount of active power and electricity losses in low-voltage electrical networks of industrial power supply systems, agrotechnical complexes, and enterprises of the public utility sector.


Author(s):  
F. P. Shkrabets

The increase in the capacity of cleaning and construction vehicles for highcapacity and energy-intensive mines calls for an increase in the  supply voltage of cleaning and tunneling combines, as well as  transport systems: from a voltage of 660 V switched to 1140 V, and  now to 3300 V. This allows improving technical and economic  indicators for clearing and access areas, as well as improving the reliability of local Power Supply Systems (PSS). However, this  trend prevents the supply of underground electric networks with a  voltage of 6 kV, in connection with which the problem arises of  increasing the voltage of supply networks. To date, it has become  possible to apply the 10 kV voltage to the operation, which is most  acceptable for the use of electrical equipment for electrical networks  and protection devices. Leading educational, research and design  organizations were engaged in research on this issue. An analysis of the results of the research showed that switching to 10 kV voltage is  justified and timely. At the same time, 35 kV voltage is not removed  from the agenda, which is technically feasible and economically  justified, but there are problems with the safety of its operation in  underground workings, which requires appropriate refinement. This  level of voltage will improve the quality of electricity.Conclusions: 1. Application of 35 kV voltage in the underground power supply system of coal and ore mines is advisable at a depth of more than 1000 m with a maximum load of at least 1000 kVA at the  level of the stem cables.2. Application of 35 kV voltage in underground electrical networks will allow to significantly improve the quality indicators of voltage,  reliability, and economy of the system due to the current unloading  of the most important element of SES, such as stem cables.3. Analysis of the main parameters and characteristics of electrical mine electrical equipment gives reason to believe that it allows  implementing a trend of 35 kV deep input to deep horizons of mines  (mines) and placement of 35/6 kV substations on working horizons.


Author(s):  
Sergey V. Belyaev ◽  
Aleksey V. Malafeev ◽  
Evgeniy Ya. Omelchenko

To ensure uninterrupted power supply to consumers, maintenance of the electrical networks in a working condition is today carried out through the use of a system of preventive maintenance. In the general case such a system allows building equipment repair schedules based on repair cycles for a long time predetermining the list of necessary material and labor resources in advance. However, in practice, the use of this system is rather difficult and not always effective. This is due to the need to change the repair schedule for emergency or urgent repairs taking into account the seasonality of work performed and the organizational structure of the production department of electrical networks and related departments as well as taking into account the specific features of the operation of specific equipment. Taking into account the current pace of development of electrical networks with a steady increase in the number of consumers (which also leads to a complication of the configuration of electrical networks) this is impossible without the use of appropriate mathematics and software that automates the planning processes for the maintenance and repair of electrical networks with a large number of factors. The minimum equipment downtime was taken as the main criterion for optimality, as a factor that largely determines the reliability of power supply. A planning algorithm has been developed that takes into account the ranking of works in order of importance, the possibility of their shift in time and the likely adjustment of the schedule based on the results of assessing the technical condition of the equipment. A method for minimizing the downtime of repair crews by using them in adjacent areas as well as a technique for identifying a set of equipment that may be under repair in the same period of time are proposed.


2021 ◽  
Vol 2131 (5) ◽  
pp. 052049
Author(s):  
V Z Manusov ◽  
M R Otuzbaev ◽  
M A Scherbinina ◽  
G V Ivanov

Abstract Assessment of the current technical condition is an important task, so the state of electrical equipment depends on its further operability. Thanks to modern computing devices, it is possible to implement actively artificial intelligence and computer-assisted learning methods that allow achieving high efficiency in data processing. A study was conducted and an algorithm for diagnosing the technical condition based on an artificial neural network was developed. A model based on a multilayer perceptron is proposed, which allows evaluating the technical condition of a high-voltage power transformer. The result of the technical diagnostics of the model is the assignment of the condition to one of the five classes, proposed by the guidelines presented by the International Council on Large Electrical Systems. The methodology is presented on the example of a 250 MVA transformer with a certain defect history, which allowed us to show the reliability and validity of the obtained results. It is shown that the use of the proposed model makes it possible to achieve accuracy in determining the technical condition of 0.95. The introduction of this model into an automated monitoring and diagnostics system will allow assessing the technical condition of electrical equipment in real time with sufficient accuracy.


Author(s):  
Vladimir Mikhailovich Levin ◽  
Ammar Abdulazez Yahya

The Bayesian classifier is a priori the optimal solution for minimizing the total error in problems of statistical pattern recognition. The article suggests using the classifier as a regular tool to increase the reliability of defect recognition in power oil-filled transformers based on the results of the analysis of gases dissolved in oil. The wide application of the Bayesian method for solving tasks of technical diagnostics of electrical equipment is limited by the problem of the multidimensional distribution of random parameters (features) and the nonlinearity of classification. The application of a generalized feature of a defect in the form of a nonlinear function of the transformer state parameters is proposed. This simultaneously reduces the dimension of the initial space of the controlled parameters and significantly improves the stochastic properties of the random distribution of the generalized feature. A special algorithm has been developed to perform statistical calculations and the procedure for recognizing the current technical condition of the transformer using the generated decision rule. The presented research results illustrate the possibility of the practical application of the developed method in the conditions of real operation of power transformers.


Author(s):  
F.Sh. Khafizov ◽  
◽  
Zh. da K. Novikova Freyre Shavier ◽  

The problem of energy security of industrial enterprises is considered, which is directly related to the technical condition of 6 kV power cables with impregnated paper insulation. The conclusion is made about the need for a unified approach to the prevention of accidents caused by faults and cable defects. The task is to conduct a study and develop an integral criterion that allows identifying the current technical condition of 6 kV power cables. To carry out these studies, a special experimental setup was created in the diagnostic laboratory of the Ufa State Petroleum Technical University. The developed research method is based on the theory of non-destructive testing. Analysis of the research results based on the analysis of input and output signals of various frequencies, taking into account the characteristics of the power cable, confirmed the fact of changes in the measured values. This indicates the presence of damage and defects inside the cable. Diagnostic parameters were obtained during the research. The relationship between these parameters and the characteristic level of cable defects and damages is established. Using an artificial neural network, integral diagnostic parameters were formed, and an integral criterion was developed. The use of this criterion will allow to identify faults and defects in power cables and track the dynamics of their development, predict the residual resource of cables, and transfer them to maintenance according to their actual condition. All this will further increase the safety and efficiency of electrical equipment operation at the industrial enterprises.


2021 ◽  
Vol 1 (2) ◽  
Author(s):  
Xuan Cuong NGO ◽  
Nhu Y DO

Explosion-proof transformers 6/1.2 kV is important electrical equipment responsible forsupplying electricity in underground mine electrical networks. A failure of this transformer will cause aninterruption in the power supply and loss of safety in underground mining. Usually, explosion-prooftransformers in underground mine electrical networks are designed and manufactured to work with idealparameters such as sinusoidal currents, and the network structure is symmetrical. However, today inunderground mine electric networks, many power electronics are connected to the network, such asinverters and soft starters. As a result, a current flowing through the transformer is non-sinusoidal,overloading the transformer even by working with the design specifications. This paper studies theinfluence of harmonics on the working efficiency of a 6/1.2 kV transformer in a pit mine. Research resultssuggest reasonable solutions for transformer operation to ensure longevity and not cause damage to thetransformer.


2020 ◽  
Vol 1 (57) ◽  
pp. 28-32
Author(s):  
V. Perepecheny

This article presents the results of research on the parameters of electrical networks with a voltage of 6 (10) and 0.38 kV in relation to capital investments. The analysis of existing methods of estimation of parameters before designing for power supply networks in a small town with low load density is carried out. In modern conditions, in the distribution of electrical networks is of paramount importance the introduction of energy-saving schemes and parameters of power supply systems. One of the main ways to implement them is to increase the efficiency of 6-10 / 0.38 kV networks. In the actual design of electrical networks, economic proportionality can not always be maintained for various reasons: the impact of technical constraints, the discreteness of the rated power of transformers and cable crossing scales, a significant deviation of individual capacities of consumers from the average value. In that case there is an increase in the reduced costs. A methodology for determining the optimal power of transformer substations and optimal sections of 0.38 kV power transmission lines is proposed, taking into account the probable nature of the applied load. When assembling the power supply circuit for the optimal form of parameters, voltage, principles of voltage regulation and reactive power compensation. Decisions of this kind are substantiated by technical and economic comparisons of a series of technically acceptable variants of power supply networks. An important measure that facilitates the selection of the most economical option is the assessment of the proposed project, which relates to the selection of the optimal capacity of transformer substation (TS) networks using calculation formulas. The aim of the research was to improve the existing methods on the basis of separate accounting of the reliability coefficient of 0.38 kV and 6-10 kV network. Key words - electric power supply network, network parameters, transformer substation, load density, line wire section, specific load, unit costs, optimum parameter, distribution networks, electric energy.


Sign in / Sign up

Export Citation Format