Exergy Analysis of Data Center Thermal Management Systems

Author(s):  
Amip J. Shah ◽  
Van P. Carey ◽  
Cullen E. Bash ◽  
Chandrakant D. Patel ◽  
Ratnesh K. Sharma
Author(s):  
Amip J. Shah ◽  
Van P. Carey ◽  
Cullen E. Bash ◽  
Chandrakant D. Patel

Data centers today contain more computing and networking equipment than ever before. As a result, a higher amount of cooling is required to maintain facilities within operable temperature ranges. Increasing amounts of resources are spent to achieve thermal control, and tremendous potential benefit lies in the optimization of the cooling process. This paper describes a study performed on data center thermal management systems using the thermodynamic concept of exergy. Specifically, an exergy analysis has been performed on sample data centers in an attempt to identify local and overall inefficiencies within thermal management systems. The development of a model using finite volume analysis has been described, and potential applications to real-world systems have been illustrated. Preliminary results suggest that such an exergy-based analysis can be a useful tool in the design and enhancement of thermal management systems.


Author(s):  
Amip J. Shah ◽  
Van P. Carey ◽  
Cullen E. Bash ◽  
Chandrakant D. Patel

As heat dissipation in data centers rises by orders of magnitude, inefficiencies such as recirculation will have an increasingly significant impact on the thermal manageability and energy efficiency of the cooling infrastructure. For example, prior work has shown that for simple data centers with a single Computer Room Air-Conditioning (CRAC) unit, an operating strategy that fails to account for inefficiencies in the air space can result in suboptimal performance. To enable system-wide optimality, an exergy-based approach to CRAC control has previously been proposed. However, application of such a strategy in a real data center environment is limited by the assumptions inherent to the single-CRAC derivation. This paper addresses these assumptions by modifying the exergy-based approach to account for the additional interactions encountered in a multi-component environment. It is shown that the modified formulation provides the framework necessary to evaluate performance of multi-component data center thermal management systems under widely different operating circumstances.


2008 ◽  
Vol 39 (7) ◽  
pp. 1023-1029 ◽  
Author(s):  
Sara McAllister ◽  
Van P. Carey ◽  
Amip Shah ◽  
Cullen Bash ◽  
Chandrakant Patel

2008 ◽  
Vol 130 (2) ◽  
Author(s):  
Amip J. Shah ◽  
Van P. Carey ◽  
Cullen E. Bash ◽  
Chandrakant D. Patel

The modeling of recirculation patterns in air-cooled data centers is of interest to ensure adequate thermal management of computer racks at increased heat densities. Most metrics that describe recirculation are based exclusively on temperature inside the data center, and therefore fail to provide adequate information regarding the energy efficiency of the thermal infrastructure. This paper addresses this limitation through an exergy analysis of the data center thermal management system. The approach recognizes that the mixing of hot and cold streams in the data center airspace is an irreversible process and must therefore lead to a loss of exergy. Experimental validation in a test data center confirms that such an exergy-based characterization in the cold aisle reflects the same recirculation trends as suggested by traditional temperature-based metrics. Further, by extending the exergy-based model to include irreversibilities from other components of the thermal architecture, it becomes possible to quantify the amount of available energy supplied to the cooling system that is being utilized for thermal management purposes. The energy efficiency of the entire data center cooling system can then be collapsed into the single metric of net exergy loss. When evaluated against a ground state of the external ambience, this metric enables an estimate of how much of the energy emitted into the environment could potentially be harnessed in the form of useful work. Thus, this paper successfully demonstrates that the proposed exergy-based approach can provide a foundation upon which the data center cooling system can be simultaneously evaluated for thermal manageability and energy efficiency.


Author(s):  
Sreekanth M. ◽  
M. Feroskhan

Exergy analysis is an advanced and a fair method of performance evaluation compared to the traditional energy analysis. In this article, a review of the exergy analysis studies carried out in the field of thermal management of electric vehicles is conducted. Studies conducted on battery, electric motor, cabin and electronics have been considered. It is noted that most of the work is done on battery thermal management. The nature of the work, methods used, parameters varied and parameters evaluated are listed. It can be found that the amount of work carried out in this field is very much limited. Hence, the scope of future work is more and is described in the conclusions.


Energies ◽  
2021 ◽  
Vol 14 (5) ◽  
pp. 1357
Author(s):  
Wei Li ◽  
Shusheng Xiong ◽  
Xiaojun Zhou ◽  
Wei Shi ◽  
Chongming Wang ◽  
...  

This paper aims to design thermal dummy cells (TDCs) that can be used in the development of lithium-ion battery thermal management systems. Based on physical property and geometry of real 18,650 cylindrical cells, a three-dimensional model of TDCs was designed, and it is used to numerically simulate the thermal performance of TDCs. Simulations show that the TDC can mimic the temperature change on the surface of a real cell both at static and dynamic current load. Experimental results show that the rate of heating resistance of TDC is less than 0.43% for temperatures between 27.5 °C and 90.5 °C. Powered by a two-step voltage source of 12 V, the temperature difference of TDCs is 1 °C and 1.6 °C along the circumference and the axial directions, respectively. Powered by a constant voltage source of 6 V, the temperature rising rates on the surface and in the core are higher than 1.9 °C/min. Afterwards, the proposed TDC was used to simulate a real cell for investigating its thermal performance under the New European Driving Cycle (NEDC), and the same tests were conducted using real cells. The test indicates that the TDC surface temperature matches well with that of the real battery during the NEDC test, while the temperature rise of TDC exceeds that of the real battery during the suburban cycle. This paper demonstrates the feasibility of using TDCs to replace real cells, which can greatly improve safety and efficiency for the development of lithium-ion battery thermal management systems.