Experimental and Analytical Investigation of Compact Liquid Cooled Heat Sinks

Author(s):  
M. Zugic ◽  
J. R. Culham ◽  
P. Teertstra ◽  
Y. Muzychka ◽  
K. Horne ◽  
...  

Compact, liquid cooled heat sinks are used in applications where high heat fluxes and boundary resistance preclude the use of more traditional air cooling techniques. Four different liquid cooled heat sink designs, whose core geometry is formed by overlapped ribbed plates, are examined. The objective of this analysis is to develop models that can be used as design tools for the prediction of overall heat transfer and pressure drop of heat sinks. Models are validated for Reynolds numbers between 300 and 5000 using experimental tests. The agreement between the experiments and the models ranges from 2.35% to 15.3% RMS.

Author(s):  
Ganesh Guggilla ◽  
Arvind Pattamatta ◽  
Ramesh Narayanaswamy

Abstract Due to the advancements in computing services such as machine learning and artificial intelligence, high-performance computing systems are needed. Consequently, the increase in electron chip density results in high heat fluxes and required sufficient thermal management to maintain the servers. In recent times, the liquid cooling techniques become prominent over air cooling as it has significant advantages. Spray cooling is one such efficient cooling process which can be implemented in electronics cooling. To enhance the knowledge of the process, detailed studies of fundamental mechanisms involved in spray cooling such as single droplet and multiple droplet interactions are required. The present work focuses on the study of a train of droplets impinging over a heated surface using FC-72 liquid. The surface temperature is chosen as a parameter, and the Dynamic Leidenfrost point (DLP) for the present impact conditions is identified. Spread hydrodynamics and heat transfer characteristics of these consecutively impinging droplets till the Leidenfrost temperature, are studied and compared.


Author(s):  
Kidus Guye ◽  
De Dong ◽  
Yunseo Kim ◽  
Hyoungsoon Lee ◽  
Baris Dogruoz ◽  
...  

Abstract Over the last several decades, cooling technologies have been developed to address the growing thermal challenges associated with high-powered electronics. However, within the next several years, the heat generated by these devices is predicted to exceed 1 kW/cm2, and traditional methods, such as air cooling, are limited in their capacities to dissipate such high heat fluxes. In contrast, two-phase cooling methods, such as microdroplet evaporation, are very promising due to the large latent heat of vaporization associated with the phase change process. Previous studies have shown non-axisymmetric droplets exhibit different evaporation characteristics than spherical droplets. For a droplet pinned atop a micropillar, the solid-liquid and liquid-vapor interfacial area, the volume, and thickness of the droplet are the major factors that govern the evaporation heat transport process. In this work, we develop a shape optimization tool using the particle swarm optimization algorithm to maximize evaporation from a droplet confined atop a micropillar. The tool is used to optimize the shape of a nonaxisymmetric droplet. Compared to droplets atop circular and regular equilateral triangular micropillar structures, we find that droplets confined on pseudo-triangular micropillar structures have 23.7% and 5.7% higher heat transfer coefficients, respectively. The results of this work will advance the design of microstructures that support droplets with maximum heat transfer performance.


Author(s):  
H. Chiba ◽  
T. Ogushi ◽  
H. Nakajima

In recent years, since heat dissipation rates and high frequency electronic devices have been increasing, a heat sink with high heat transfer performance is required to cool these devices. Heat sink utilizing micro-channels with several ten microns are expected to provide an excellent cooling performance because of their high heat transfer capacities due to small channel. Therefore, various porous materials such as cellular metals have been investigated for heat sink applications. However, heat sink using conventional porous materials has a high pressure drop because the cooling fluid flow through the pores is complex. Among the described porous materials, a lotus-type porous metal with straight pores is preferable for heat sinks due to the small pressured drop. In present work, cooling performance of the lotus copper heat sink for air cooling and water cooling is introduced. The experimental data for air cooling show 13.2 times higher than that for the conventional groove fins. And, the data for the water cooling show 1.7 times higher than that for the micro-channels. It is concluded that lotus copper heat sink is the most prospective candidate for high power electronics devices.


Author(s):  
Aalok Trivedi ◽  
Nikhil Lakhkar ◽  
Madhusudhan Iyengar ◽  
Michael Ellsworth ◽  
Roger Schmidt ◽  
...  

With the continuing industry trends towards smaller, faster and higher power devices, thermal management continues to be extremely important in the development of electronics. In this era of high heat fluxes, air cooling still remains the primary cooling solution in desktops mainly due to its cost. The primary goal of a good thermal design is to ensure that the chip can function at its rated frequency or speed while maintaining the junction temperature within the specified limit. The first and foremost step in measurement of thermal resistance and hence thermal characterization is accurate determination of junction temperature. Use of heat sinks as a thermal solution is well documented in the literature. Previously, the liquid cooled cold plate tester was studied using a different approach and it was concluded that the uncertainty in heat transfer coefficient was within 8% with errors in appropriate parameters, this result was supported by detailed uncertainty analysis based on Monte-Carlo simulations. However, in that study the tester was tested computationally. In this paper, testing and characterization of a heat sink tester is presented. Heat sinks were tested according to JEDEC JESD 16.1 standard for forced convection. It was observed that the error between computational and experimental values of thermal resistances was 10% for the cases considered.


2006 ◽  
Vol 956 ◽  
Author(s):  
Oleg A. Voronov ◽  
Gary S. Tompa ◽  
Veronika Veress

ABSTRACTWhile absolute power levels in microelectronic devices are relatively modest (a few tens to a few hundred watts), heat fluxes can be significant (through 50 W/cm2 in current electronic chips and up to 2000 W/cm2 in semiconductor lasers). Diamond heat sinks enable heat transfer rates well above what is possible with standard thermal management devices. We have fabricated heat sinks using diamond, which has the highest temperature thermal conductivity of any known material. Polycrystalline diamonds manufactured by chemical vapor deposition (CVD) are machined by laser and combined with metallic or ceramic tiles. Cooling by fluid flow through micro-channels enhances heat removal. These unique attributes make diamond based heat sinks prime contenders for the next generation of high heat load sinks. Such devices could be utilized for efficient cooling in a variety of applications requiring high heat transfer capability, including semiconductor lasers, microprocessors, multi-chip modules in computers, laser-diode arrays, radar systems, and high-flux optics, among other applications. This paper will review test designs, heat flux measuring system, and measured heat removal values.


2016 ◽  
Vol 138 (9) ◽  
Author(s):  
Yangying Zhu ◽  
Dion S. Antao ◽  
Kuang-Han Chu ◽  
Siyu Chen ◽  
Terry J. Hendricks ◽  
...  

We investigated the role of surface microstructures in two-phase microchannels on suppressing flow instabilities and enhancing heat transfer. We designed and fabricated microchannels with well-defined silicon micropillar arrays on the bottom heated microchannel wall to promote capillary flow for thin film evaporation while facilitating nucleation only from the sidewalls. Our experimental results show significantly reduced temperature and pressure drop fluctuation especially at high heat fluxes. A critical heat flux (CHF) of 969 W/cm2 was achieved with a structured surface, a 57% enhancement compared to a smooth surface. We explain the experimental trends for the CHF enhancement with a liquid wicking model. The results suggest that capillary flow can be maximized to enhance heat transfer via optimizing the microstructure geometry for the development of high performance two-phase microchannel heat sinks.


2005 ◽  
Vol 128 (6) ◽  
pp. 557-563 ◽  
Author(s):  
Paul L. Sears ◽  
Libing Yang

Heat transfer coefficients were measured for a solution of surfactant drag-reducing additive in the entrance region of a uniformly heated horizontal cylindrical pipe with Reynolds numbers from 25,000 to 140,000 and temperatures from 30to70°C. In the absence of circumferential buoyancy effects, the measured Nusselt numbers were found to be in good agreement with theoretical results for laminar flow. Buoyancy effects, manifested as substantially higher Nusselt numbers, were seen in experiments carried out at high heat flux.


Author(s):  
Jensen Hoke ◽  
Todd Bandhauer ◽  
Jack Kotovsky ◽  
Julie Hamilton ◽  
Paul Fontejon

Liquid-vapor phase change heat transfer in microchannels offers a number of significant advantages for thermal management of high heat flux laser diodes, including reduced flow rates and near constant temperature heat rejection. Modern laser diode bars can produce waste heat loads >1 kW cm−2, and prior studies show that microchannel flow boiling heat transfer at these heat fluxes is possible in very compact heat exchanger geometries. This paper describes further performance improvements through area enhancement of microchannels using a pyramid etching scheme that increases heat transfer area by ∼40% over straight walled channels, which works to promote heat spreading and suppress dry-out phenomenon when exposed to high heat fluxes. The device is constructed from a reactive ion etched silicon wafer bonded to borosilicate to allow flow visualization. The silicon layer is etched to contain an inlet and outlet manifold and a plurality of 40μm wide, 200μm deep, 2mm long channels separated by 40μm wide fins. 15μm wide 150μm long restrictions are placed at the inlet of each channel to promote uniform flow rate in each channel as well as flow stability in each channel. In the area enhanced parts either a 3μm or 6μm sawtooth pattern was etched vertically into the walls, which were also scalloped along the flow path with the a 3μm periodicity. The experimental results showed that the 6μm area-enhanced device increased the average maximum heat flux at the heater to 1.26 kW cm2 using R134a, which compares favorably to a maximum of 0.95 kw cm2 dissipated by the plain walled test section. The 3μm area enhanced test sections, which dissipated a maximum of 1.02 kW cm2 showed only a modest increase in performance over the plain walled test sections. Both area enhancement schemes delayed the onset of critical heat flux to higher heat inputs.


Author(s):  
Pei-Xue Jiang ◽  
Zhi-Hui Li ◽  
Chen-Ru Zhao

This paper presents the experimental and numerical investigation results of the convection heat transfer of CO2 at supercritical pressures in a 0.0992 mm diameter vertical tube at various inlet Reynolds numbers, heat fluxes and flow directions. The effects of buoyancy and flow acceleration resulted from the dramatic properties variation were investigated. Results showed that the local wall temperature varied non-linearly for both upward and downward flow when the heat flux was high. The difference of the local wall temperature between upward flow and downward flow was very small when other test conditions were held the same, which indicates that for supercritical CO2 flowing in a mini tube as employed in this study, the buoyancy effect on the convection heat transfer was quite insignificant, and the flow acceleration induced by the axial density variation with temperature was the main factor that lead to the abnormal local wall temperature distribution at high heat fluxes. The predicted values using the LB low Reynolds number turbulence model correspond well with the measured data. Velocity profiles and turbulence kinetic energy near the wall varying along the tube generated by the numerical simulations were presented to develop a better understanding.


Author(s):  
Jianyun Shuai ◽  
Rudi Kulenovic ◽  
Manfred Groll

Flow boiling in small-sized channels attracted extensive investigations in the past two decades due to special requirements for transfer of high heat fluxes from narrow spaces in various industrial applications. Experiments on various aspects of flow boiling in narrow channels were carried out and theoretical attempts were undertaken. But these investigations showed large differences, e.g. up till now the knowledge on the development of flow patterns in small non-circular flow passages is very limited. This paper deals with investigations on flow boiling of water in two rectangular channels with dimensions (width×depth) 2.0×4.0 mm2 and 0.5×2.0 mm2 (corresponding hydraulic diameters are 2.67 mm and 0.8 mm). The pressure at the test section exit is atmospheric. For steady-state experimental conditions the effects of heat flux, mass flux and inlet subcooling on the boiling heat transfer coefficient and the pressure drop are investigated. Flow patterns and the transition of flow patterns along the channel axis are visualized and documented with a video-camera. Bubbly flow, slug flow and annular flow are distinguished in both channels. Preliminary flow pattern maps are generated.


Sign in / Sign up

Export Citation Format

Share Document